Plan Review Notes For Permit 18090327 |
Permit Number |
18090327 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2019-02-01 18:57:20 | BUILDING REVIEW PROVISO: | | 1-PROVIDE WINDOW W11CUT SHEETS SHOWING COMPLIANCE WITH | | ALL EGRESS CLEAR OPENINGS (36"X62" MAY NOT COMPLY). | | 2- PROVIDE COMPLETE FRAMING DETAILS FOR WINDOWS IN THE | | DORMER AREA. | | 3- PROVIDE ICC EVALUATION REPORT FOR "POLYISO SPRAY | | FOAM". | | 4- PROVIDE PRODUCT APPROVAL FOR: A) PRECAST LINTELS. | | B)HARDIE PLANK LAP SIDING & CEMENT BOARD TRIM. C) | | WINDOW MULLIONS AND SPECIFY MULLION SIZES. | | 5-REVISE ENERGY CALCULATIONS: A)A/C AREA TO MATCH | | PLANS. B)INSULATION ON ITEM #8 TO MATCH PLANS. C) | | INSULATION ON EXTERIOR & INTERIOR WALLS TO MATCH PLANS | | D)WHERE IS THE 6 X 7 WOOD DOOR. E)DOORS WITH GLAZING | | NEED TO BE COUNTED IN THE WINDOW AREA. F)REVISE WINDOWS | | ORIENTATION, OVERHANG DEPTH AND SEPARATION TO MATCH | | PLANS. NOTE: LABEL FOR WINDOWS/DOORS SHOWING THE | | U-FACTOR AND SHGC FACTOR IS REQUIRED. |
|