Plan Review Notes
Plan Review Notes For Permit 18090327
Permit Number 18090327
Review Stop P
Sequence Number 2
Notes
Date Text
2018-10-15 11:07:221ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PLEASE INDICATE ON THE PLAN THE CURRENT CODE FBC
 PLUMBING, FUEL GAS 2017 6TH EDITION.
  
 2. SHT. P. 4 THE SOIL STACK FOR THE MASTER BATHROOM ON
 SECOND FLOOR SHALL CONNECT DOWN STREAM OF THE BATHROOM
 GROUPS 4 + 5 PER FBC PL 912.1
  
 3. SHT. P. 4 THE TUB AND SHOWER CANNOT CONNECT TOGETHER
 BEFORE CONNECTING TO THE WET VENT THEY SHALL CONNECT
 SEPARATELY TO THE BUILDING DRAIN BRANCH ONLY ONE
 FIXTURE CAN CONNECT UPSTREAM OF THE LAVATORY. PER FBC
 PL 912.1, 912.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  