2018-10-15 11:07:22 | 1ST REVIEW: | | 2017 FLORIDA BUILDING CODE 6TH EDITION | | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION | | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH | | EDITION | | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH | | EDITION | | | | PLUMBING COMMENTS: | | | | 1. PLEASE INDICATE ON THE PLAN THE CURRENT CODE FBC | | PLUMBING, FUEL GAS 2017 6TH EDITION. | | | | 2. SHT. P. 4 THE SOIL STACK FOR THE MASTER BATHROOM ON | | SECOND FLOOR SHALL CONNECT DOWN STREAM OF THE BATHROOM | | GROUPS 4 + 5 PER FBC PL 912.1 | | | | 3. SHT. P. 4 THE TUB AND SHOWER CANNOT CONNECT TOGETHER | | BEFORE CONNECTING TO THE WET VENT THEY SHALL CONNECT | | SEPARATELY TO THE BUILDING DRAIN BRANCH ONLY ONE | | FIXTURE CAN CONNECT UPSTREAM OF THE LAVATORY. PER FBC | | PL 912.1, 912.2.1 | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT | | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID | | THE PREVIOUSLY REVIEWED SHEETS. | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|