Notes |
Date |
Text |
2018-12-04 10:56:06 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | NO SMOKE ALARMS SHOWN | | | | PLEASE SHOW LOCATIONS OF BOTH PANELS | | | | INTE SYSTEM BONDING STRIP NOT SHOWN. | | | | NO LOW VOLTAGE SYSTEMS SHOWN | | | | SITE PLAN SHOWS TWO BUIDINGS IS THERE ELECTRIC TO THE | | SECOND TWO STORY BUILDING? DISCONNECT AND GROUNDING??? |
|