2018-10-15 11:29:05 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHT. P.4 UNDER NNATURAL GAS NOTES IT LIST TOTAL |
| PROPANE BTU'S THE REST OF THE PLAN INDICATES NATURAL |
| GAS PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 2. SHT. P.4 THE FIRST SECTION OF PIPE FROM THE METER TO |
| THE TEE FOR WATER HEATER SHALL BE 1" PER FBC FG TABLE |
| 402.4(2) |
| |
| 3. SHT. P.4 ON THE RISER SHOW THE SYSTEM PRESSURE AND |
| THE TYPE OF PIPE. PER WPB AMEND TO FBC 107.2.1 |
| |
| 4. SHT. P.4 UNDER ATURAL GAS NOTES IT LIST THE CODE AS |
| 2014 THE CURRENT CODE IS FBC FG 2017 6TH EDITION. |
| PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 5. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| |
| 6. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR |
| 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES |
| DRYERS). |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |