Plan Review Notes For Permit 18090327 |
Permit Number |
18090327 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-09-27 13:02:50 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | NO SMOKE ALARMS SHOWN | | | | E-1 RISER SHOWS OVERHEAD TO PANEL IF THIS IS TRUE THEN | | A MAIN DISCONNECT WILL BE REQUIRED OUTSIDE AT METER. | | NO INTERSYSTEM BONDING STRIP SHOWN, PANELS SHOW | | 240/3/60? | | | | E-4 LOAD CALCULATION IS NOT PER ARTICLE 220 OF THE | | NEC., NO GFCI SHOWN FOR POOL, NO GFCI AND AFCI FOR | | WIRING IN HOUSE. |
|