2018-09-27 13:02:50FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 NO SMOKE ALARMS SHOWN
  
 E-1 RISER SHOWS OVERHEAD TO PANEL IF THIS IS TRUE THEN
 A MAIN DISCONNECT WILL BE REQUIRED OUTSIDE AT METER.
 NO INTERSYSTEM BONDING STRIP SHOWN, PANELS SHOW
 240/3/60?
  
 E-4 LOAD CALCULATION IS NOT PER ARTICLE 220 OF THE
 NEC., NO GFCI SHOWN FOR POOL, NO GFCI AND AFCI FOR
 WIRING IN HOUSE.