2018-11-01 19:02:43 | NEW SINGLE FAMILY RESIDENCE (R3) BUILDING REVIEW |
| COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1-IMPACT FEES - DIGITAL SUBMITTALS |
| |
| PLANS WILL BE REVIEWED BY THE PBC IMPACT FEE OFFICE |
| DIGITALLY VIA PROJECTDOX UPON NOTIFICATION BY THIS |
| OFFICE. NOTIFICATION MAY OCCUR WHEN PLANS ARE NEAREST |
| FINAL FORM. YOU MAY COORDINATE WITH THE IMPACT FEE |
| OFFICE AT (561) 233-5025 OR SIMPLY UPLOAD THE MUNICIPAL |
| IMPACT FEE QUESTIONNAIRE FORM TO YOUR PROJECT AND NAME |
| THE FILE MUNICIPAL IMPACT FEE QUESTIONNAIRE. THE FORM |
| CAN BE FOUND AT: HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINIS |
| TRATION/PDF/IMPACTFEES/FORMS/QUESTIONNAIRE.PDF UPON |
| APPROVAL AND FEE PAYMENT, PLEASE UPLOAD THE RECEIPT TO |
| YOUR PROJECT OR EMAIL IT TO [email protected] |
| |
| 2- PROVIDE DRAINAGE PLAN SHOWING COMPLIANCE WITH THE |
| FOLLOWING: |
| FBC R 401.3 (DRAINAGE) |
| FBC 107.2.5 (SITE PLAN) |
| FBC 110.9 (IMPACT OF CONSTRUCTION) |
| |
| SEC. R401.3 FBC_RESIDENTIAL: |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| DOES NOT CREATE A HAZARD. LOTS SHALL BE GRADED TO DRAIN |
| SURFACE WATER AWAY FROM FOUNDATION WALLS. THE GRADE |
| SHALL FALL A MINIMUM OF 6 INCHES (152 MM) WITHIN THE |
| FIRST 10 FEET (3048 MM). |
| EXCEPTION: WHERE LOT LINES, WALLS, SLOPES OR OTHER |
| PHYSICAL BARRIERS PROHIBIT 6 INCHES (152 MM) OF FALL |
| WITHIN 10 FEET (3048 MM), DRAINS OR SWALES SHALL BE |
| CONSTRUCTED TO ENSURE DRAINAGE AWAY FROM THE STRUCTURE. |
| IMPERVIOUS SURFACES WITHIN 10 FEET (3048 MM) OF THE |
| BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF 2 |
| PERCENT AWAY FROM THE BUILDING. |
| |
| 107.2.5 SITE PLAN. THE CONSTRUCTION DOCUMENTS SUBMITTED |
| WITH THE APPLICATION FOR PERMIT SHALL BE ACCOMPANIED BY |
| A SITE PLAN SHOWING TO SCALE THE SIZE AND LOCATION OF |
| NEW CONSTRUCTION AND EXISTING STRUCTURES ON THE SITE, |
| DISTANCES FROM LOT LINES, THE ESTABLISHED STREET GRADES |
| AND THE PROPOSED FINISHED GRADES, DEPICTING THE |
| PROPOSED LOT DRAINAGE AND, AS APPLICABLE, FLOOD HAZARD |
| AREAS, FLOODWAYS, AND DESIGN FLOOD ELEVATIONS; AND IT |
| SHALL BE DRAWN IN ACCORDANCE WITH AN ACCURATE AND |
| INCLUDED ON A BOUNDARY LINE SURVEY. IN THE CASE OF |
| DEMOLITION, THE SITE PLAN SHALL SHOW CONSTRUCTION TO BE |
| DEMOLISHED AND THE LOCATION AND SIZE OF EXISTING |
| STRUCTURES AND CONSTRUCTION THAT ARE TO REMAIN ON THE |
| SITE OR PLOT. THE BUILDING OFFICIAL IS AUTHORIZED TO |
| WAIVE OR MODIFY THE REQUIREMENT FOR A SITE PLAN WHEN |
| THE |
| APPLICATION FOR PERMIT IS FOR ALTERATION OR REPAIR OR |
| WHEN OTHERWISE WARRANTED. |
| |
| SEC. 110.9 CITY AMENDMENTS: IMPACT OF CONSTRUCTION. ALL |
| CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE |
| PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE |
| CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS |
| PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO A CONSENT |
| GRANTED BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS |
| OR CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY |
| OWNER. THIS INCLUDES, BUT IS NOT LIMITED TO, THE |
| CONTROL OF DUST, NOISE, WATER OR DRAINAGE RUN-OFFS, |
| DEBRIS, AND THE STORAGE OF CONSTRUCTION MATERIALS. NEW |
| CONSTRUCTION ACTIVITY SHALL NOT ADVERSELY IMPACT LEGAL |
| HISTORIC SURFACE WATER DRAINAGE FLOWS SERVING ADJACENT |
| PROPERTIES, AND MAY REQUIRE SPECIAL DRAINAGE DESIGN |
| COMPLYING WITH ENGINEERING STANDARDS TO PRESERVE THE |
| POSITIVE DRAINAGE PATTERNS OF THE AFFECTED SITES. |
| ACCORDINGLY, DEVELOPERS, CONTRACTORS AND OWNERS OF ALL |
| NEW RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, |
| POOLS, PATIOS, DRIVEWAYS, DECKS |
| OR SIMILAR ITEMS, ON EXISTING PROPERTIES RESULTING IN A |
| SIGNIFICANT DECREASE OF PERMEABLE LAND AREA ON ANY |
| PARCEL OR HAS ALTERED THE DRAINAGE FLOW ON THE |
| DEVELOPED PROPERTY SHALL, AS A PERMIT CONDITION, |
| PROVIDE A PROFESSIONALLY PREPARED DRAINAGE PLAN CLEARLY |
| INDICATING COMPLIANCE WITH THIS PARAGRAPH. UPON |
| COMPLETION OF THE IMPROVEMENT, A CERTIFICATION FROM A |
| LICENSED PROFESSIONAL SHALL BE SUBMITTED TO THE |
| INSPECTOR IN ORDER TO RECEIVE APPROVAL OF THE FINAL |
| INSPECTION. |
| |
| |
| 3- ART IN PUBLIC SPACES. |
| PLEASE REVIEW ART IN PUBLIC PLACES. THE CITY OF WEST |
| PALM BEACH ART IN PUBLIC PLACES ORDINANCE REQUIREMENT |
| THAT APPLIES TO ANY REMODEL OR NEW CONSTRUCTION PROJECT |
| FOR WHICH THE PERMIT APPLICATION WAS SUBMITTED AFTER |
| 6/29/14, AND THE TOTAL PROJECT CONSTRUCTION COSTS ARE |
| EQUAL TO OR GREATER THAN $750,000 WILL NEED TO COMPLY |
| WITH THIS ORDINANCE. |
| PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| PROJECT CONSTRUCTION COST. |
| PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| PROJECTS. |
| FOR CONTACT INFORMATION PLEASE CONTACT: |
| MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| 822-1515 E-MAIL: [email protected] |
| |
| 4- SURVEY: |
| A) FLOOD INFORMATION. ACCORDING TO NEW FEMA MAPS |
| EFFECTIVE 10/05/2017 THE PROPOSED HOUSE IS LOCATED IN |
| TWO FLOOD ZONES. SURVEY ONLY SHOW ONE. PROVIDE |
| INFORMATION FOR BOTH ZONES ON SURVEY WITH PROPOSED |
| HOUSE. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| B) SURVEYOR NOTE #10 REFERENCES VERTICAL DATUM NGVD 29. |
| NEED TO BE BE REVISED BASED ON THE VERTICAL DATUM OF |
| NEW FLOOD MAPS EFFECTIVE 10/05/2017. REVISE AS |
| REQUIRED. |
| |
| C) NEED TO PROVIDE HARD COPY OF SURVEY WITH ORIGINAL |
| SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 472 F. S. OR |
| SUBMIT SURVEY DIGITALLY SIGNED. COORDINATE WITH CITY |
| LIBRARIAN (LAURA MARCHANT (561)805-6658 OR CAROLINE |
| PUELL (561)805-6659) FOR PROPER UPLOADING. |
| |
| 5-SINGLE HUNG WINDOWS W5 (2'-4"X5'-0") AND W3 |
| (2'-8"X5'-0") DON'T SEEM TO COMPLY WITH ALL EGRESS |
| REQUIREMENTS OF SEC. R310.2.1 FBC-RESIDENTIAL. REVISE |
| SIZE OF WINDOW AS REQUIRED OR PROVIDE MANUFACTURER CUT |
| SHEETS SHOWING COMPLIANCE WITH THE EGRESS REQUIREMENTS |
| FOR SIZE OF WINDOWS SPECIFIED. |
| |
| 6- A)DESIGN CRITERIA ON SHEET S-0.01 SPECIFIES "B" |
| BUILDING EXPOSURE. ACCORDING TO SEC. R301.2.1.4 AND |
| SEC. R301.2.1.4.3 FBC-RESIDENTIAL THIS BUILDING IS |
| LOCATED IN EXPOSURE "C" NOT "B". REVISE AS REQUIRED. |
| NOTE: SURFACE ROUGHNESS NEED TO BE FOR 1500 FEET FOR |
| EACH WIND DIRECTION IN ORDER TO BE CONSIDERED EXPOSURE |
| B CATEGORY. |
| |
| B) REVISE THE COMPONENTS AND CLADDING DESIGN PRESSURES |
| SPECIFIED ON SHEET S-0.03. NEED TO SPECIFY DESIGN |
| PRESSURES FOR EXPOSURE "C". AND, CLEARLY SPECIFY THE |
| ULTIMATE (VULT) AND NOMINAL (VASD) WIND LOADS. SEC. |
| R301.2.1.3 FBC-RESIDENTIAL. |
| NOTE: PRODUCT APPROVALS WILL BE REVIEWED ONCE DESIGN |
| PRESSURES ARE REVISED. |
| |
| 7- DESIGN LOADS ON SHEET S-0.01 DON'T MATCH WOOD TRUSS |
| LOADING ON SHEET S-0.02. REVISE AS REQUIRED TO MATCH |
| AND SPECIFY THE ATTIC LIVE LOAD AS REQUIRED BY TABLE |
| R301.5 FBC-RESIDENTIAL. SEE NOTES "B" AND "G" OF TABLE |
| R301.5. |
| |
| 8- HIGH ROOF FRAMING PLAN SHEET S-1.02: CLARIFY |
| CONNECTOR FOR TRUSS GIRDER TG2. IS LOOKS LIKE IT'S MGT |
| NOT MTG. REVISE AS REQUIRED. SEC. 107.2.1 CITY |
| AMENDMENTS. |
| |
| 9- PROVIDE DETAILS AND SPECIFICATIONS FOR STRUCTURAL |
| BUCK DETAILS SHOWING COMPLIANCE WITH SEC. R609.7.2.1 |
| FBC-RESIDENTIAL. |
| |
| 10-CLARIFY WOOD BEAM TO WOOD POST CONCEALED CONNECTOR |
| SPECIFIED ON DETAIL 3 AND 4 ON SHEET S-3.02. SIMPSON |
| CBT2Z IS FOR 4X4 POST NOT FOR 8X8 POST. CLARIFY/REVISE |
| AS REQUIRED. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 11- A)IT LOOKS LIKE GUARDRAILS ARE REQUIRED ON PORCHES. |
| REVISE PLANS AS REQUIRED AND PROVIDE COMPLETE DETAILS |
| AND SPECIFICATIONS. SEC. R312.1.1 FBCD-RESIDENTIAL. |
| |
| B) HANDRAIL IS REQUIRED IN GARAGE STEPS AND PORCHES . |
| SEC. R311.7.8 FBC-RESIDENTIAL. PROVIDE COMPLETE DETAILS |
| AND SPECIFICATIONS. |
| |
| 12- PROVIDE COMPLETE FRAMING DETAILS AND SPECIFICATIONS |
| FOR WINDOWS IN THE DORMER AREA. SPECIFY ALL FRAMING |
| MEMBERS AND CONNECTORS. SEC. R301.1 FBC-RESIDENTIAL. |
| |
| 13- PROVIDE DETAILS AND SPECIFICATIONS FOR THE |
| INSTALLATION OF THE CEDAR SHUTTERS SHOWN ON PLANS. SEC. |
| R301.1 FBC-RESIDENTIAL. |
| |
| 14-SPECIFY ATTIC ACCESS SIZE FOR ATTIC ACCESS SHOWN ON |
| FIRST FLOOR AND SECOND FLOOR. SEC. R807 |
| FBC-RESIDENTIAL. |
| |
| 15- PROVIDE SPECIFICATIONS FOR GARAGE DOOR LEADING TO |
| THE INTERIOR OF THE HOUSE TO COMPLY WITH SEC. R302.5.1 |
| FBC-RESIDENTIAL. |
| |
| 16- PLANS TO SPECIFY CEILINGS AND INTERIOR WALL |
| (BETWEEN GARAGE AND MAIN HOUSE) INSULATION R VALUE. |
| SEC. R103.2 FBC-ENERGY CONSERVATION. NOTE: COORDINATE |
| WITH ENERGY CALCULATIONS TO AVOID CONFLICTS/DELAYS. |
| |
| 17- SOIL TEST REPORT: NEED TO PROVIDE HARD COPY OF SOIL |
| TEST REPORT WITH ORIGINAL SEAL AND SIGNATURE AS |
| REQUIRED BY CHAPTER 471 F. S. OR SUBMIT REPORT |
| DIGITALLY SIGNED. COORDINATE WITH CITY LIBRARIAN (LAURA |
| MARCHANT (561)805-6658 OR CAROLINE PUELL (561)805-6659) |
| FOR PROPER UPLOADING. |
| |
| 18- PROVIDE ICC EVALUATION REPORT FOR "POLYISO SPRAY |
| FOAM" SPECIFIED ON PLANS TO SHOW COMPLIANCE WITH SEC. |
| R316 FBC-RESIDENTIAL. |
| NOTE: ICC REPORT TO BE REVIEWED AND APPROVED BY THE |
| ARCHITECT OF RECORD PRIOR TO SUBMITTAL TO THIS OFFICE. |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL) |
| |
| 19- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| 61G20-3.001 FOR: |
| (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| SUBMITTAL) |
| |
| A) PRECAST LINTELS |
| |
| B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS |
| AND DETAILS. NOTE: PROVIDE ONLY THE FLORIDA PRODUCT |
| APPROVAL COVER PAGE AND PAGE SHOWING THE SPECIFIED |
| CONNECTOR OR DESIGN PROFESSIONAL TO LIST THE FLORIDA |
| PRODUCT APPROVAL NUMBER NEXT TO EACH SPECIFIED |
| CONNECTOR. |
| |
| C)HARDIE PLANK LAP SIDING AND CEMENT BOARD TRIM AS |
| SHOWN ON ELEVATIONS. |
| |
| D) WINDOW MULLIONS AS SHOWN ON PLANS. REQUIRED: CLEARLY |
| SPECIFY MULLION SIZE TO BE USED TO VERIFY COMPLIANCE |
| WITH THE CALCULATED DESIGN PRESSURES. |
| |
| E) NOTE: PROVIDE THE FLORIDA PRODUCT APPROVAL COVER |
| PAGES THAT CORRESPOND TO DRAWINGS SUBMITTED FOR THE |
| ENTRY DOOR, GARAGE SIDE DOOR, KITCHEN DOOR AND FRENCH |
| DOORS SHOWN ON PLANS. |
| |
| 20-DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| |
| 21-REVISE ENERGY CALCULATIONS. SEC. R101.5.1.1.2 |
| FBC-ENERGY CONSERVATION. COORDINATE WITH ARCHITECT TO |
| AVOID CONFLICTS/DELAYS. |
| A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM, |
| INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE, |
| ETC. |
| |
| B) A/C AREA SHOWN ON ITEM #6 DOESN'T MATCH PLANS. |
| |
| C) INSULATION ON SLAB ON GRADE AND FLOOR OVER OTHER |
| SPACE ON ITEM #8 DOESN'T MATCH PLANS. |
| |
| D) R VALUE INSULATION ON EXTERIOR AND INTERIOR WALLS |
| DON'T MATCH PLANS. NOTE: ALSO NOTE THAT ADJACENT WALL |
| IS PARTIAL METAL FRAMING AND PARTIAL MASONRY. SEE |
| PLANS. |
| |
| E)CLARIFY NUMBER OF PEOPLE SPECIFIED ON PAGE 2 OF 5. |
| HOW MAY PEOPLE ARE IN THE 3 BEDROOM HOUSE. EIGHT |
| PEOPLE?. 4 UPSTAIRS AND 4 DOWNSTAIRS?. TYPICALLY, THE |
| NUMBER OF PEOPLE IS TAKEN BASED ON THE NUMBER OF |
| BEDROOMS. |
| IT LOOKS LIKE COUNTING THE PEOPLE TWICE. WHY? |
| |
| F) CLARIFY WHERE IS THE 6 FEET BY 7 FEET WOOD DOOR |
| SPECIFIED ON PAGE OF 5. COORDINATE WITH PLANS AND |
| PRODUCT APPROVALS SUBMITTED. |
| |
| G)WINDOWS AND DOORS WITH GLAZING ARE NOT VINYL. REVISE |
| MATERIAL ON WINDOWS INFORMATION AS REQUIRED. AS |
| REQUIRED. SEE PLANS AND PRODUCT APPROVALS SUBMITTED. |
| |
| H)DOORS WITH GLAZING NEED TO BE CONSIDERED IN THE |
| WINDOW AREA. REVISE AS REQUIRED. SEE SEC. R405.5.3.3 |
| FBC-ENERGY CONSERVATION. |
| |
| I) REVISE WINDOWS OVERHANG DEPTH AND SEPARATION TO |
| MATCH PLANS. |
| |
| J)NEED TO PROVIDE HARD COPY OF ENERGY CALCULATIONS WITH |
| ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY CHAPTER 472 |
| F. S. OR SUBMIT REPORT DIGITALLY SIGNED. COORDINATE |
| WITH CITY LIBRARIAN (LAURA MARCHANT (561)805-6658 OR |
| CAROLINE PUELL (561)805-6659) FOR PROPER UPLOADING. |
| |
| NOTE: |
| LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND |
| SHGC FACTOR IS REQUIRED WHEN THE ENERGY CALCULATIONS |
| ARE NOT USING THE DEFAULT FACTOR. |
| |
| |
| |
| |
| ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| |