2018-12-20 10:34:59 | MECHANICAL PROVISOS: | | | | 1) PROVIDE A LETTER FROM THE MANUFACTURER CERTIFYING | | THE INSTALLATION OF THE EXTERIOR CONDENSER IN THE | | ENCLOSED GARAGE. | | | | 2) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION | | INSTRUCTIONS FOR THE DWYER CO AND NO2 SENSORS IN THE | | ENCLOSED PARKING GARAGE SHALL BE ONSITE AT TIME OF | | INSPECTION. | | | | 3) GARAGE EXHAUST SYSTEM TEST REQUIRED AT FINAL | | INSPECTION. | | | | 4) MIAMI-DADE NOA FOR THE EXHAUST LOUVERS SHALL BE | | ONSITE AT TIME OF INSPECTION. |
|