Plan Review Notes
Plan Review Notes For Permit 18090262
Permit Number 18090262
Review Stop M
Sequence Number 2
Notes
Date Text
2018-12-20 10:34:59MECHANICAL PROVISOS:
  
 1) PROVIDE A LETTER FROM THE MANUFACTURER CERTIFYING
 THE INSTALLATION OF THE EXTERIOR CONDENSER IN THE
 ENCLOSED GARAGE.
  
 2) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE DWYER CO AND NO2 SENSORS IN THE
 ENCLOSED PARKING GARAGE SHALL BE ONSITE AT TIME OF
 INSPECTION.
  
 3) GARAGE EXHAUST SYSTEM TEST REQUIRED AT FINAL
 INSPECTION.
  
 4) MIAMI-DADE NOA FOR THE EXHAUST LOUVERS SHALL BE
 ONSITE AT TIME OF INSPECTION.