2018-10-04 16:00:55 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18090262 |
| 10/4/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| MULTI-SPLIT AC SYSTEM- SECTION C403.2.1 FBC-17 ENERGY |
| CONSERVATION. |
| |
| 2) SHEET GM301: VERIFY THE GARAGE EXHAUST TERMINATION |
| LOCATIONS ARE IN COMPLIANCE WITH THE REQUIRED |
| CLEARANCES LISTED UNDER SECTIONS 501.3 & 501.3.1 FBC M. |
| |
| 3) GM301: CLARIFY HOW MAKEUP AIR IS BEING PROVIDED FOR |
| THE GARAGE EXHAUST- SECTION 501.4 FBC M. |
| |
| 4) GM301: THE AIR HANDLER APPEARS TO BE LOCATED IN THE |
| HOISTWAY ENCLOSURE WHICH IS PROHIBITED PER SECTION |
| 3002.9 FBC B. |
| |
| 5) GM301: THE CONDENSING UNIT FOR THE MULTI-SPLIT |
| SYSTEM IS DESIGNED, AND LISTED AND LABELED FOR OUTDOOR |
| INSTALLATION. PLEASE RELOCATE THE CONDENSER TO THE |
| OUTDOORS PER THE MANUFACTURER'S SPECIFICATIONS- SECTION |
| 304.1 FBC M. |
| |
| 6) CLARIFY IF HOISTWAY VENTING WILL BE PROVIDED AND |
| PROVIDE DETAILS IF APPLICABLE. |
| |
| 7) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE CO2 AND |
| NO2 SENSORS, AND THE CONTROLLER. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |