Plan Review Notes
Plan Review Notes For Permit 18090245
Permit Number 18090245
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-09-14 15:20:48THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) THERE ARE NO CLEAR INDICATIONS OF LIGHTNING
 PROTECTION.
  
 LIGHTNING PROTECTION SHALL COMPLY WITH NFPA 780,
 INSTALLATION OF LIGHTNING PROTECTION SYSTEMS
  
 CHAPTER 12 PROTECTION FOR SOLAR ARRAYS
 12.1 GENERAL. THE INTENT OF THIS CHAPTER SHALL BE TO
 PROVIDE
 LIGHTNING PROTECTION REQUIREMENTS FOR ROOF-MOUNTED OR
 GROUND-MOUNTED SOLAR (PHOTOVOLTAIC AND THERMAL) PANELS.
 12.2 FUNDAMENTAL PRINCIPLES OF PROTECTION.
 12.2.1 ROOF-MOUNTED OR GROUND-MOUNTED SOLAR PANELS
 SUBJECT
 TO DIRECT LIGHTNING STRIKE SHALL BE PROTECTED IN
 ACCORDANCE
 WITH CHAPTER 4 AND AS SUPPLEMENTED IN THIS CHAPTER.
 12.2.2 PROTECTION SHALL BE PROVIDED BY ONE OR MORE OF
 THE
 FOLLOWING METHODS:
 (1) DIRECT MOUNTING OF STRIKE TERMINATION DEVICES TO
 THE SOLAR
 PANEL
 (2) DIRECT MOUNTING OF STRIKE TERMINATION DEVICES TO
 THE SOLAR
 PANEL FRAMING
 (3) LOCATING STRIKE TERMINATION DEVICES (INCLUDING AIR
 TERMINALS,
 MASTS, AND OVERHEAD GROUND WIRES) ADJACENT TO THE
 SOLAR PANELS IN SUCH A MANNER AS TO PLACE THE SOLAR
 PANELS
 IN A ZONE OF PROTECTION AS DEFINED IN SECTION 4.8
 12.3 STRIKE TERMINATION DEVICES.
 12.3.1 STRIKE TERMINATION DEVICES SHALL EXTEND A
 MINIMUM OF
 10 IN. (254 MM) VERTICALLY ABOVE THE APEX OF THE SOLAR
 PANEL.
 12.3.2 STRIKE TERMINATION DEVICES SHALL BE LOCATED AT
 THE ENDS
 OF THE UPPERMOST EDGE OR NEAREST SUPPORT OF PITCHED
 SOLAR
 PANELS OR PANEL ARRAYS NOT TO EXCEED 2 FT (0.6 M) FROM
 THE END
 OF THE PANEL OR ARRAY UNLESS THE UPPERMOST EDGE OR
 NEAREST
 SUPPORT IS WITHIN A ZONE OF PROTECTION.
 12.3.3 STRIKE TERMINATION DEVICES SHALL BE LOCATED
 ALONG THE
 UPPERMOST EDGE OF SOLAR PANELS OR PANEL ARRAYS AT
 INTERVALS NOT
 EXCEEDING 20 FT (6 M) UNLESS THE PANEL ARRAYS ARE
 WITHIN A ZONE
 OF PROTECTION.
  
  
 PLEASE PROVIDE THE REQUIRED PROTECTION.
  
  
 2) THE POWER DICONNECT SHALL BE CLEARED MARKED WITH
 AREA DIRECTIONAL SIGNAGE IF NEEDED.
  
  
 PETER LEDUC
 FIRE MARSHAL