Plan Review Notes
Plan Review Notes For Permit 18090225
Permit Number 18090225
Review Stop P
Sequence Number 1
Notes
Date Text
2018-10-10 16:57:201ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE DISCHARGE FROM THE STEAM UNIT SHALL DISCHARGE
 THRU AN AIR GAP INTO A WASTE RECEPTOR NOT A FLOOR DRAIN
 . FBC PL 802.2 AND THE WASTE RECEPTOR CANNOT BE
 INSTALLED IN CONCEALED SPACES. WASTE RECEPTORS SHALL
 NOT BE INSTALLED IN PLENUMS, CRAWL SPACES, ATTICS,
 INTERSTITIAL SPACES ABOVE CEILINGS AND BELOW FLOORS.
 READY ACCESS SHALL BE PROVIDED TO WASTE RECEPTORS. THE
 WASTE RECEPTOR SHALL BE INSTALLED IN A CLOSET OR OPEN
 AREA PER FBC PL 802.3
  
 2. ON SHT P2-90-14A IT NOTES THAT THE STEAM UNIT IS BY
 OTHERS IF THIS IS CORRECT A SEPARATE PERMIT WILL BE
 REQUIRED. PLACE NOTE ON PLAN. PER WPB AMEND TO FBC
 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  