Date |
Text |
2018-10-10 16:57:20 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. THE DISCHARGE FROM THE STEAM UNIT SHALL DISCHARGE |
| THRU AN AIR GAP INTO A WASTE RECEPTOR NOT A FLOOR DRAIN |
| . FBC PL 802.2 AND THE WASTE RECEPTOR CANNOT BE |
| INSTALLED IN CONCEALED SPACES. WASTE RECEPTORS SHALL |
| NOT BE INSTALLED IN PLENUMS, CRAWL SPACES, ATTICS, |
| INTERSTITIAL SPACES ABOVE CEILINGS AND BELOW FLOORS. |
| READY ACCESS SHALL BE PROVIDED TO WASTE RECEPTORS. THE |
| WASTE RECEPTOR SHALL BE INSTALLED IN A CLOSET OR OPEN |
| AREA PER FBC PL 802.3 |
| |
| 2. ON SHT P2-90-14A IT NOTES THAT THE STEAM UNIT IS BY |
| OTHERS IF THIS IS CORRECT A SEPARATE PERMIT WILL BE |
| REQUIRED. PLACE NOTE ON PLAN. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |
| GEORGE JOHNSON |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561-805-6711 |
| [email protected] |
| |