Plan Review Notes
Plan Review Notes For Permit 18090225
Permit Number 18090225
Review Stop E
Sequence Number 1
Notes
Date Text
2018-09-25 07:27:34FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PROVISIO
  
 SUBMIT THE FOLLOWING INFORMATION PRIOR TO THE FIANL
 ELECTRCAL INSPECTION.
  
 ADDED LOAD NEEDS TO BE CALCULATED INTO THE LOAD CALC
 FOR THIS UNIT. STEAM UNIT. PLAN SHOWS 100A TO STEAM
 UNIT PANEL SCHEDULE SHOWS 70A?
  
 TV ADDED IN THE BATH AREA 406.9(C) OUTLET NOT ALLOWED
 IN BATH OR SHOWER AREA.
  
 REVISION SHOWS NO ADDED VALUE? (STEAM UNIT)