2019-06-17 10:11:042ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18090217
 9/27/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED
  
 THE RESULTS FROM THE 1ST REVIEW COMMENTS ARE INDICATED
 BELOW.
  
 1) OK
  
 2) OK
  
 3) STILL EXISTS- GENERAL SCOPE OF WORK NOTES ON NEW M-1
 SHEET INCLUDES THE PAINT SPRAY BOOTH. (PLEASE NOTE THAT
 A SEPARATE PERMIT IS REQUIRED FOR THE SPRAY BOOTH SO IT
 WILL NOT BE REVIEWED AT THIS TIME. THE CONTRACTOR OF
 RECORD SHALL SUBMIT A SEPARATE APPLICATION AND TWO SETS
 OF PLANS AND SPECIFICATIONS FOR REVIEW.)
  
 4) STILL EXISTS- NO CONTRACT OR DOCUMENTATION SUBMITTED
 TO VERIFY COSTS. (THE $50,000 JOB VALUE ON THE PERMIT
 APPLICATION APPEARS LOW FOR THE SCOPE OF THE PROPOSED
 PROJECT. PLEASE SUBMIT DETAILED ESTIMATES AND/OR BONA
 FIDE CONTRACTS FOR ALL PHASES OF THE PROJECT INCLUDING
 STRUCTURAL, ELECTRIC, MECHANICALL, PLUMBING, INTERIOR
 AND EXTERIOR FINISH, SITE WORK, DESIGN FEES, AND OVER
 HEAD AND PROFIT. PLEASE NOTE VALUE IS BASED ON LABOR,
 MATERIALS, AND EQUIPMENT.)
  
 5) STILL EXISTS- NEW SHEETS A-1 & A-2 SHOW THE 15000
 CFM COLLECTOR LOCATED 8'4" TO THE ROLL UP DOOR. WHETHER
 NEW OR EXISTING, PROVIDE DOCUMENTATION INDICATING THE
 DOOR IS IMPACT RESISTANT AND CAPABLE OF RESISTING THE
 CURRENT WINDSPEEDS AND PRESSURES PER THE ASCE 7-10- SEE
 SECTION 1609 FBC B. (SHEET A2: THE PLAN DOES NOT
 CLEARLY SHOW THAT THE LOCATIONS OF THE NEW COLLECTORS
 ARE IN COMPLIANCE WITH SECTION 511.1 FBC M WHICH
 REQUIRES A MINIMUM 10' CLEARANCE TO COMBUSTIBLE
 CONSTRUCTION AND ALSO UNPROTECTED OPENINGS INTO THE
 BUILDINGS.)
  
 6) STILL EXISTS- BASED ON COMMENT 35 ABOVE, A METAL
 VENT PIPE MAY BE REQUIRED TO BE LOCATED ABOVE THE
 HIGHEST ROOF LEVEL WITH A DISTANCE OF 30'- SECTION
 511.1 FBC M. (A-2, M3, & M4: THE COLLECTOR DRAWINGS ARE
 INCONSISTENT ON HOW THE COLLECTION, EXHAUST, AND RETURN
 SYSTEMS ARE FUNCTIONING. THERE ARE NO EXHAUST
 DISCHARGES SHOWN, OR LABELED FOR THE COLLECTORS,
 HOWEVER THERE APPEARS TO BE A RETURN AIR DUCT INTO THE
 BUILDING AS SHOWN ON SHEETS A2 & M3. PLEASE VERIFY
 COMPLIANCE WITH SECTION 511.1.3).
  
 7) STILL EXISTS- SPACING OF HANGERS AND ATTRACHMENT TO
 THE STRUCTURE NOT PROVIDED (PROVIDE TYPICAL DETAILS FOR
 DUCT HANGING AND SUPPORT INCLUDING SPACING OF THE
 HANGERS,).
  
 8) STILL EXISTS- NOT PROVIDED SHEETS S1 & M3: THE
 STRUCTURAL ENGINEER OF RECORD MUST PROVIDE COMPLETE
 DETAILS FOR CONSTUCTION OF THE STEEL FRAIMING AND
 SUPPORT BASES FOR THE COLLECTORS INCLUDING WIND LOAD
 ENGINEERING FOR ATTACHING THE COLLECTORS TO THE
 SUPPORTS AND THE SUPPORTS TO THE FOUNDATIONS- SECTION
 301.15 FBC M.).
  
 9) STILL EXISTS- NOT PROVIDED (A FLORIDA LICENSED
 MECHANICAL CONTRACTOR SHALL SUBMIT A SUB-PERMIT
 APPLICATION FOR INSTALLATION OF THE DUCT COLLECTORS AND
 DUCT SYSTEMS- SECTION 489.113 (I) FS.).
  
 10) NEW COMMENT: SHOW THE LOCATION OF THE REQUIRED
 EXPLOSION RELIEF VENT- SECTION 511.1.5 FBC M.
  
 11) NEW COMMENT, SHEET M-3: MUCH OF THE PRINT IN THE
 MAXI-FILTER DETAILS IS TOO FAINT TO READ AND SCAN INTO
 THE CITY'S COMPUTER FILES- SECTION 107.2.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER