Date |
Text |
2019-06-17 10:11:04 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT #18090217 |
| 9/27/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED |
| |
| THE RESULTS FROM THE 1ST REVIEW COMMENTS ARE INDICATED |
| BELOW. |
| |
| 1) OK |
| |
| 2) OK |
| |
| 3) STILL EXISTS- GENERAL SCOPE OF WORK NOTES ON NEW M-1 |
| SHEET INCLUDES THE PAINT SPRAY BOOTH. (PLEASE NOTE THAT |
| A SEPARATE PERMIT IS REQUIRED FOR THE SPRAY BOOTH SO IT |
| WILL NOT BE REVIEWED AT THIS TIME. THE CONTRACTOR OF |
| RECORD SHALL SUBMIT A SEPARATE APPLICATION AND TWO SETS |
| OF PLANS AND SPECIFICATIONS FOR REVIEW.) |
| |
| 4) STILL EXISTS- NO CONTRACT OR DOCUMENTATION SUBMITTED |
| TO VERIFY COSTS. (THE $50,000 JOB VALUE ON THE PERMIT |
| APPLICATION APPEARS LOW FOR THE SCOPE OF THE PROPOSED |
| PROJECT. PLEASE SUBMIT DETAILED ESTIMATES AND/OR BONA |
| FIDE CONTRACTS FOR ALL PHASES OF THE PROJECT INCLUDING |
| STRUCTURAL, ELECTRIC, MECHANICALL, PLUMBING, INTERIOR |
| AND EXTERIOR FINISH, SITE WORK, DESIGN FEES, AND OVER |
| HEAD AND PROFIT. PLEASE NOTE VALUE IS BASED ON LABOR, |
| MATERIALS, AND EQUIPMENT.) |
| |
| 5) STILL EXISTS- NEW SHEETS A-1 & A-2 SHOW THE 15000 |
| CFM COLLECTOR LOCATED 8'4" TO THE ROLL UP DOOR. WHETHER |
| NEW OR EXISTING, PROVIDE DOCUMENTATION INDICATING THE |
| DOOR IS IMPACT RESISTANT AND CAPABLE OF RESISTING THE |
| CURRENT WINDSPEEDS AND PRESSURES PER THE ASCE 7-10- SEE |
| SECTION 1609 FBC B. (SHEET A2: THE PLAN DOES NOT |
| CLEARLY SHOW THAT THE LOCATIONS OF THE NEW COLLECTORS |
| ARE IN COMPLIANCE WITH SECTION 511.1 FBC M WHICH |
| REQUIRES A MINIMUM 10' CLEARANCE TO COMBUSTIBLE |
| CONSTRUCTION AND ALSO UNPROTECTED OPENINGS INTO THE |
| BUILDINGS.) |
| |
| 6) STILL EXISTS- BASED ON COMMENT 35 ABOVE, A METAL |
| VENT PIPE MAY BE REQUIRED TO BE LOCATED ABOVE THE |
| HIGHEST ROOF LEVEL WITH A DISTANCE OF 30'- SECTION |
| 511.1 FBC M. (A-2, M3, & M4: THE COLLECTOR DRAWINGS ARE |
| INCONSISTENT ON HOW THE COLLECTION, EXHAUST, AND RETURN |
| SYSTEMS ARE FUNCTIONING. THERE ARE NO EXHAUST |
| DISCHARGES SHOWN, OR LABELED FOR THE COLLECTORS, |
| HOWEVER THERE APPEARS TO BE A RETURN AIR DUCT INTO THE |
| BUILDING AS SHOWN ON SHEETS A2 & M3. PLEASE VERIFY |
| COMPLIANCE WITH SECTION 511.1.3). |
| |
| 7) STILL EXISTS- SPACING OF HANGERS AND ATTRACHMENT TO |
| THE STRUCTURE NOT PROVIDED (PROVIDE TYPICAL DETAILS FOR |
| DUCT HANGING AND SUPPORT INCLUDING SPACING OF THE |
| HANGERS,). |
| |
| 8) STILL EXISTS- NOT PROVIDED SHEETS S1 & M3: THE |
| STRUCTURAL ENGINEER OF RECORD MUST PROVIDE COMPLETE |
| DETAILS FOR CONSTUCTION OF THE STEEL FRAIMING AND |
| SUPPORT BASES FOR THE COLLECTORS INCLUDING WIND LOAD |
| ENGINEERING FOR ATTACHING THE COLLECTORS TO THE |
| SUPPORTS AND THE SUPPORTS TO THE FOUNDATIONS- SECTION |
| 301.15 FBC M.). |
| |
| 9) STILL EXISTS- NOT PROVIDED (A FLORIDA LICENSED |
| MECHANICAL CONTRACTOR SHALL SUBMIT A SUB-PERMIT |
| APPLICATION FOR INSTALLATION OF THE DUCT COLLECTORS AND |
| DUCT SYSTEMS- SECTION 489.113 (I) FS.). |
| |
| 10) NEW COMMENT: SHOW THE LOCATION OF THE REQUIRED |
| EXPLOSION RELIEF VENT- SECTION 511.1.5 FBC M. |
| |
| 11) NEW COMMENT, SHEET M-3: MUCH OF THE PRINT IN THE |
| MAXI-FILTER DETAILS IS TOO FAINT TO READ AND SCAN INTO |
| THE CITY'S COMPUTER FILES- SECTION 107.2.1 WPB. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |