2018-09-27 18:26:54 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18090217 |
| 9/27/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) DESIGN CRITERIA: PROVIDE A LIST OF CURRENT CODES AND |
| STANDARDS USED IN THE DESIGN OF THE PROJECT- SECTION |
| 107.2.1 WPB. |
| |
| 2) PROVIDE ON THE PLAN THE LEVEL OF ALTERATION AS |
| OUTLINED IN CHAPTER 5 FBC EX. |
| |
| 3) PLEASE NOTE THAT A SEPARATE PERMIT IS REQUIRED FOR |
| THE SPRAY BOOTH SO IT WILL NOT BE REVIEWED AT THIS |
| TIME. THE CONTRACTOR OF RECORD SHALL SUBMIT A SEPARATE |
| APPLICATION AND TWO SETS OF PLANS AND SPECIFICATIONS |
| FOR REVIEW. |
| |
| 4) THE $50,000 JOB VALUE ON THE PERMIT APPLICATION |
| APPEARS LOW FOR THE SCOPE OF THE PROPOSED PROJECT. |
| PLEASE SUBMIT DETAILED ESTIMATES AND/OR BONA FIDE |
| CONTRACTS FOR ALL PHASES OF THE PROJECT INCLUDING |
| STRUCTURAL, ELECTRIC, MECHANICALL, PLUMBING, INTERIOR |
| AND EXTERIOR FINISH, SITE WORK, DESIGN FEES, AND OVER |
| HEAD AND PROFIT. PLEASE NOTE VALUE IS BASED ON LABOR, |
| MATERIALS, AND EQUIPMENT. |
| |
| 5) SHEET A2: THE PLAN DOES NOT CLEARLY SHOW THAT THE |
| LOCATIONS OF THE NEW COLLECTORS ARE IN COMPLIANCE WITH |
| SECTION 511.1 FBC M WHICH REQUIRES A MINIMUM 10' |
| CLEARANCE TO COMBUSTIBLE CONSTRUCTION AND ALSO |
| UNPROTECTED OPENINGS INTO THE BUILDINGS. |
| |
| 6) A-2, M3, & M4: THE COLLECTOR DRAWINGS ARE |
| INCONSISTENT ON HOW THE COLLECTION, EXHAUST, AND RETURN |
| SYSTEMS ARE FUNCTIONING. THERE ARE NO EXHAUST |
| DISCHARGES SHOWN, OR LABELED FOR THE COLLECTORS, |
| HOWEVER THERE APPEARS TO BE A RETURN AIR DUCT INTO THE |
| BUILDING AS SHOWN ON SHEETS A2 & M3. PLEASE VERIFY |
| COMPLIANCE WITH SECTION 511.1.3: |
| |
| 511.1.3 CONVEYING SYSTEMS EXHAUST DISCHARGE. |
| AN EXHAUST SYSTEM SHALL DISCHARGE TO THE OUTSIDE OF THE |
| BUILDING EITHER DIRECTLY BY FLUE OR INDIRECTLY THROUGH |
| THE BIN OR VAULT INTO WHICH THE SYSTEM DISCHARGES |
| EXCEPT WHERE THE CONTAMINANTS HAVE BEEN REMOVED. |
| EXHAUST SYSTEM DISCHARGE SHALL BE PERMITTED TO BE |
| RECIRCULATED PROVIDED THAT THE SOLID PARTICULATE HAS |
| BEEN REMOVED AT A MINIMUM EFFICIENCY OF 99.9 PERCENT AT |
| 10 MICRONS (10.01 MM), VAPOR CONCENTRATIONS ARE LESS |
| THAN 25 PERCENT OF THE LFL, AND APPROVED EQUIPMENT IS |
| USED TO MONITOR THE VAPOR CONCENTRATION. |
| |
| 7) PROVIDE TYPICAL DETAILS FOR DUCT HANGING AND SUPPORT |
| INCLUDING SPACING OF THE HANGERS, |
| |
| 8) SHEETS S1 & M3: THE STRUCTURAL ENGINEER OF RECORD |
| MUST PROVIDE COMPLETE DETAILS FOR CONSTUCTION OF THE |
| STEEL FRAIMING AND SUPPORT BASES FOR THE COLLECTORS |
| INCLUDING WIND LOAD ENGINEERING FOR ATTACHING THE |
| COLLECTORS TO THE SUPPORTS AND THE SUPPORTS TO THE |
| FOUNDATIONS- SECTION 301.15 FBC M. |
| |
| 9) A FLORIDA LICENSED MECHANICAL CONTRACTOR SHALL |
| SUBMIT A SUB-PERMIT APPLICATION FOR INSTALLATION OF THE |
| DUCT COLLECTORS AND DUCT SYSTEMS- SECTION 489.113 (I) |
| FS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |
2018-09-27 17:55:35 | |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |