Plan Review Notes
Plan Review Notes For Permit 18090217
Permit Number 18090217
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-09-17 10:37:13THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THE SUBMITTED PLAN SHEETS WHERE NOT PROVIDED WITH
 ANY KIND OF ORDER AND WERE NOT ORGAINIZED OR BOUND
 TOGETHER AS SETS.
  
 PER NFPA 1
  
 1.7.11 PLANS AND SPECIFICATIONS.
  
 1.7.11.1 THE AHJ SHALL HAVE THE AUTHORITY TO REQUIRE
 PLANS AND SPECIFICATIONS TO ENSURE COMPLIANCE WITH
 APPLICABLE CODES AND STANDARDS.
  
  
 PLEASE REVIEW AND PROVIDE COMPLETED SETS IN AN
 ORGANIZED MANNER
  
  
  
 2) THERE ARE NO INDICATIONS OF A FIRE SPRINKLER SYSTEM
 IN EITHER OF THE BUILDINGS.
  
 PER NFPA 1, CHAPTER 13, FIRE PROTECTION SYSTEMS
  
 13.3.2.28 WOODWORKING OPERATIONS. AN APPROVED AUTOMATIC
 FIRE SPRINKLER SYSTEM SHALL BE INSTALLED IN BUILDINGS
 CONTAINING
 WOODWORKING OPERATIONS EXCEEDING 2500 FT2 (232 M2) THAT
 USE
 EQUIPMENT, MACHINERY, OR APPLIANCES; THAT GENERATE
 FINELY DIVIDED
 COMBUSTIBLE WASTE; OR THAT USE FINELY DIVIDED
 COMBUSTIBLE
 MATERIALS.
  
 PLEASE REVIEW AND PROVIDE FOR THE REQUIREMENT OF
 JUSTIFY,
  
  
 CHAPTER 40 DUST EXPLOSION AND FIRE PREVENTION
  
 40.1 GENERAL. EQUIPMENT, PROCESSES, AND OPERATIONS THAT
 INVOLVE
 THE MANUFACTURE, PROCESSING, BLENDING, REPACKAGING, OR
 HANDLING
 OF COMBUSTIBLE PARTICULATE SOLIDS OR COMBUSTIBLE DUSTS
 REGARDLESS
 OF CONCENTRATION OR PARTICLE SIZE SHALL BE INSTALLED
 AND MAINTAINED
 IN ACCORDANCE WITH THIS CHAPTER AND THE FOLLOWING
 STANDARDS AS
 APPLICABLE:
 (1) NFPA 61, STANDARD FOR THE PREVENTION OF FIRES AND
 DUST
 EXPLOSIONS IN AGRICULTURAL AND FOOD PROCESSING
 FACILITIES
 (2) NFPA 69, STANDARD ON EXPLOSION PREVENTION SYSTEMS
 (3) NFPA 85, BOILER AND COMBUSTION SYSTEMS HAZARDS CODE
 (4) NFPA 120, STANDARD FOR FIRE PREVENTION AND CONTROL
 IN
 COAL MINES
 (5) NFPA 484, STANDARD FOR COMBUSTIBLE METALS
 (6) NFPA 654, STANDARD FOR THE PREVENTION OF FIRE AND
 DUST
 EXPLOSIONS FROM THE MANUFACTURING, PROCESSING, AND
 HANDLING OF COMBUSTIBLE PARTICULATE SOLIDS
 (7) NFPA 655, STANDARD FOR PREVENTION OF SULFUR FIRES
 AND
 EXPLOSIONS
 (8) NFPA 664, STANDARD FOR THE PREVENTION OF FIRES AND
 EXPLOSIONS IN WOOD PROCESSING AND WOODWORKING
 FACILITIES
  
  
  
  
 3) THERE ARE NO INDICATIONS THAT THE PROPOSED PROJECT
 IS IN COMPLIANCE OR REVIEWED THROUGH THE REQUIREMENTS
 OF NFPA 664
  
 PER NFPA 1, CHAPTER 31, FOREST PRODUCTS
  
 31.1* GENERAL. THE STORAGE, MANUFACTURING, AND
 PROCESSING OF
 TIMBER, LUMBER, PLYWOOD, VENEERS, AND BY-PRODUCTS SHALL
 BE IN
 ACCORDANCE WITH THIS CHAPTER AND NFPA 664, STANDARD FOR
 THE
 PREVENTION OF FIRES AND EXPLOSIONS IN WOOD PROCESSING
 AND
 WOODWORKING FACILITIES.
  
 31.3.9 WOOD PROCESSING AND WOODWORKING FACILITIES. DUST
 CONTROL
 SHALL BE IN ACCORDANCE WITH NFPA 664 FOR COMBUSTIBLE
 DUSTPRODUCING
 OPERATIONS THAT OCCUPY AREAS OF MORE THAN 5000 FT2 (464
 M2), OR TO AREAS WHERE DUST-PRODUCING EQUIPMENT
 REQUIRES AN
 AGGREGATE DUST COLLECTION FLOW RATE OF MORE THAN 1500
 FT3/MIN (2549
 M3/HR).
  
  
 PLEASE REVIEW AND PROVIDE A NOTE OF ACKNOWLEDGEMENT OF
 COMPLIANCE OR JUSTIFY THAT IT IS NOT REQUIRED WITH
 SPECIFIC CODE REFERENCES
  
  
  
  
 4) THERE IS NO INDICATION OF A COMPLIANCE OPTION PER
 NFPA 664.
  
 4.7 COMPLIANCE OPTIONS.
 4.7.1 OPTIONS. LIFE SAFETY, PROPERTY PROTECTION, AND
 MISSION
 CONTINUITY MEETING THE GOALS AND OBJECTIVES OF SECTION
 4.1 AND
 SECTION 4.6 SHALL BE PROVIDED IN ACCORDANCE WITH EITHER
 OF THE
 FOLLOWING:
 (1) PERFORMANCE-BASED PROVISIONS PER 4.7.2
 (2) PRESCRIPTIVE-BASED PROVISIONS PER 4.7.3
  
  
 PLEASE REVIEW AND PROVIDE SPECIFIC DETAILS.
  
  
  
 5) THERE IS AN INDICATION OF A SPRAY BOOTH AS PART OF
 THIS SUBMITTAL
  
 THE SPRAY BOOTH SHALL BE SUBMITTED UNDER SEPARATE SHOP
 DRAWINGS.
  
 PLEASE SUBMIT SEPARATE SHOP DRAWINGS FOR THE PROPOSED
 SPRAY BOOTH.
  
  
  
  
 6) THERE IS NO INDICATIONS OF FIRE PROTECTION OF THE
 PROPOSED SPRAY BOOTH.
  
 PER NFPA 1
  
 CHAPTER 43 SPRAYING, DIPPING, AND COATING USING
 FLAMMABLE OR COMBUSTIBLE MATERIALS
  
 43.1 APPLICATION.
 43.1.1* OPERATIONS INVOLVING THE SPRAY APPLICATION OF
 FLAMMABLE
 AND COMBUSTIBLE MATERIALS SHALL COMPLY WITH NFPA 33,
 STANDARD
 FOR SPRAY APPLICATION USING FLAMMABLE OR COMBUSTIBLE
 MATERIALS, AND SECTION 43.1.
  
 43.1.7 PROTECTION.
 43.1.7.1* GENERAL. SPRAY AREAS, WHICH INCLUDE BY
 DEFINITION ANY
 ASSOCIATED EXHAUST PLENUMS AND EXHAUST DUCTWORK, ANY
 PARTICULATE
 FILTERS, ANY SOLVENT CONCENTRATOR UNITS, ANY
 RECIRCULATION AIR SUPPLY
 UNITS, AND MIXING ROOMS, SHALL BE PROTECTED WITH AN
 APPROVED
 AUTOMATIC FIRE PROTECTION SYSTEM.
  
 PLEASE PROVIDE FOR THE REQUIRED PROTECTION OR JUSTIFY
 WHY NOT WITH SPECIFIC CODE REFERENCES.
  
  
  
  
 7) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 8) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  