Review Stop E
Sequence Number 1
Notes
Date Text
2018-09-24 10:04:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PLAN IS REQUIRED TO BE DESIGNED BY AN ELECTRICAL
 ENGINEER AS IT EXCEEDS THE VALUES PERMITTED IN FLORIDA
 STATUTE 471.003(2)(H).
 2. PLAN PROVIDED SHOWS INSTALLATIONS FOR DIFFERENT
 BUIDLINGS WHICH HAVE A DIFFERENT ADDRESS. THERE SHOULD
 BE TWO PERMIT APPLICATION, ONE FOR EACH ADDRESS.
 PROVIDE SECOND PERMIT APPLICATION WITH PERTINENT
 INFORMATION FOR EACH PROJECT. REMOVE ANY INFORMATION
 FROM THIS PACKET WHICH DOES NOT PERTAIN TO 435 SOUTHERN
 BLVD. WPB FBC 105.1
 3. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
 4. BUILDING PLANS SHALL BE DRAWN TO A MINIMUM 1/8 INCH
 SCALE UPON SUBSTANTIAL PAPER, CLOTH OR OTHER ACCEPTABLE
 MEDIUM. PROVIDE CORRECTION. WPB FBC 107.2.1.3
 5. PROVIDE LOAD CALCULATION FOR SERVICE, INCLUDE
 EXISTING AND NEW LOADS TO CONFIRM CAPACITY OF SERVICE
 IS ADEQUATE. NEC 215.2, 220, 408.30
 6. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF
 SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE,
 WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY
 SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW
 INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230,
 250.50, 250.94, 408.30
 7. PROVIDE PANEL SCHEDULE FOR EACH PANEL INDICATING ANY
 NEW OR ALTERED CIRCUITS, THE WIRE AND BREAKER SIZE FOR
 THESE CIRCUITS, AND AFCI OR GFCI PROTECTION WHERE
 APPLICABLE TO COMPLY WITH CODE. NEC 210.8, 210.12,
 210.19, 210.20, 215.5, 408.4
 8. PROVIDE AIC RATING OF EACH PANEL. NEC 110.3, 110.9
 9. PROVIDE AIC CALCULATION FOR EACH NEW PANEL
 INSTALLED. NEC 110.10
 10. PLAN SHOWS A NEUTRAL CONDUCTOR GOING TO 80KVA
 TRANSFORMER. PROVIDE CORRECTION. NEC 250.30
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER