Plan Review Notes
Plan Review Notes For Permit 18090217
Permit Number 18090217
Review Stop B
Sequence Number 1
Notes
Date Text
2018-10-19 07:57:20****CORRECTIONS****
 W.P.B. PERMIT: 18090217
 REVIEWED: OCTOBER 18, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC AMENDED 107.2.5]SUPPLY A SEPARATE PERMIT
 APPLICATION WITH SEPARATE ADDRESS FOR WEST BUILDING.
  
 2. [FBC AMENDED 107.2.5]THE PROPOSED STRUCTURE ON THE
 EAST SIDE OF PARKING AREA IS ON THE PROPERTY LINE.
 WHILE THE SAME OWNER HOLDS BOTH PARCELS, A UNITY OF
 TITLE WOULD NEED TO COMBINE THE PROPERTY INTO ONE
 PARCEL.
 SUBMIT APPLICATION TO THE ENGINEERING DEPARTMENT:
 HTTP://WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS/FOR
 MS,-PERMITS-APPLICATIONS
 IF THIS HAS ALREADY BEEN DONE, PLEASE PROVIDE A COPY OF
 THE RECORDED DOCUMENT.
  
 3. [FBC AMENDED 107.2.5]SHEET S-1 HAS SECTION CUTS THAT
 REFER TO SHEET S-2. PLEASE PROVIDE SHEET S-2 TO SHOW
 THE REST OF THE STRUCTURE. I SEE FOUNDATION AND I-BEAM
 POSTS, BUT I CAN?T TELL WHAT THE POSTS ARE FOR. IS
 THERE A ROOF STRUCTURE? FULL REVIEW WILL BE COMPLETED
 UPON RECEIPT OF ALL DRAWINGS. ALSO, CO-ORDINATE WITH A
 SHEETS SO SIZES AND ELEVATIONS MATCH.
  
 4. [FBC AMENDED 107.2.5]UPDATE SHEET S-1 STRUCTURAL
 DESIGN CRITERIA AND CODE.
 D-3 PROVIDE LOADS FOR THIS PROJECT.
 D-4 THE STRUCTURES ARE NOT ENCLOSED
  
 5. [FBC 401.4]PROVIDE COPY OF GEOTECHNICAL REFERENCED
 IN GEOTECHNICAL AND FOUNDATIONS F-1
  
 6. [FBC 1609.1]PROVIDE DETAILS OF HOW EQUIPMENT IS
 ATTACHED TO THE PAD.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  