Notes |
Date |
Text |
2018-11-14 14:56:49 | 1) THERE ARE MULTIPLE COPIES OF SURVEYS THAT SHOW THE | | GENERATOR IN DIFFERENT LOCATIONS. SUBMIT TWO COPIES OF | | A CLEAN SURVEY WITHOUT ITEMS CROSSED OUT THAT CLEARLY | | SHOW THE LOCATION OF THE GENERATOR. 2017 FBC SEC. | | 107.2.1. 2ND REQUEST. | | 2) THIS SUBMITTAL IS DISORGANIZED AND CONFUSING. THERE | | ARE MULTIPLE COPIES OF SHEETS AND I HAVE NO IDEA WHICH | | SHEETS ARE APPLICABLE AND WHICH ARE NOT. COMPILE THE | | DOCUMENTS INTO TWO SETS OF COMPLETE PLANS FOR SUBMITTAL | | AND REVIEW. 2017 FBC SEC. 107.1. 2ND REQUEST. | | 3) REMOVE ALL OLD DOCUMENTS FROM THE SUBMITTAL PACKAGE. | | 2017 FBC SEC. 107.2.1. THERE ARE STILL TWO DIFFERENT | | GAS DRAWINGS IN THIS SUBMITTAL PACKAGE. 2ND REQUEST. | | 4) DIFFERENT SURVEYS SHOW THE GAS METER AS NEW AND ALSO | | AS EXISTING. WHICH IS IT? CLARIFY ON THE SURVEYS. 2ND | | REQUEST. | | 5) A FEW OF THE SURVEYS SHOW THE GAS METER LABELED AS | | METER #2. ARE THERE TWO GAS METERS ON THIS PROPERTY? IF | | SO, SHOW BOTH METERS ON THE SURVEY. IF NOT, DELETE THE | | LABELING ON THE SURVEY. 2017 FBC SEC. 107.2.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|