Plan Review Notes
Plan Review Notes For Permit 18090178
Permit Number 18090178
Review Stop G
Sequence Number 1
Notes
Date Text
2018-09-19 06:44:5609/19/2018 1ST GAS REVIEW**DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THERE IS AN EXISTING GAS SYSTEM AND IT NEEDS TO ADD
 THE BTU LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED
 TO THE TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE
 EXISTING SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE
 EXISTING SYSTEM MUST BE REDONE TO ENSURE A SAFE
 OPERATING SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM
 THAT SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES,
 2017 FBC FUEL GAS RES. SECS.G2412.4, G2412.8, G2413.1,
 G2413.2, G2413.3.
  
 2. I HAVE PUT AN ISOMETRIC DRAWING FOR THE PRIOR SYSTEM
 FOR REFERENCE ONLY IF YOU LIKE ME TO EMAIL YOU A COPY
 JUST EMAIL ME AND I WILL, SUBMIT AN ISOMETRIC DRAWING
 THAT CLEARLY SHOWS THE LENGTH OF ALL CUT SECTIONS OF
 PIPE PER 2017 FBC FUEL GAS RES SECS. G2413.4.1,
 G2413.4.2.
  
 3. THE BTU LOAD FOR THE GENERATOR IS LABELED AS 330,000
 BTU AND THE MANUAL SAYS OTHERWISE, PLEASE CORRECT, WPB
 AMENDMENTS TO THE FBC SEC. 107.2.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  