2019-01-18 16:17:23 | ALL COMMENTS CLEAR EXCEPT FOR BASE FLOOD ELEVATION |
| (BFE). |
| |
| THE CITY OF WEST PALM BEACH HAS APPROVED AN ORDINANCE |
| WITH PROVISIONS ABOVE THE FEMA MINIMUM STANDARDS. ALL |
| NEW COMMERCIAL STRUCTURES SUBMITTED AFTER OCTOBER 5, |
| 2017 WILL FOLLOW THE ORDINANCES GUIDELINES FOR FLOOD |
| PLAIN MANAGEMENT. |
| |
| ORDINANCE NO. 4729-17 SEC. 18-34 - TECHNICAL AMENDMENTS |
| TO FLORIDA BUILDING CODE, BUILDING. 1612.4.2 ELEVATION |
| REQUIREMENTS. THE MINIMUM ELEVATION REQUIREMENTS SHALL |
| BE AS SPECIFIED IN ASCE 24 OR THE BASE FLOOD ELEVATION |
| PLUS TWO FEET. WHICHEVER IS HIGHER. |
| |
| ENCLOSURES BELOW THE LOWEST FLOOR. UNIT 5, SECTION E |
| COVERED THE REQUIRE-MENTS FOR OPENINGS IN ENCLOSURES. |
| IF AN APPLICANT DESIGNS AN ENCLOSURE BELOW THE LOWEST |
| FLOOR USING AN ALTERNATIVE TO THE NFIP STANDARD, A |
| REGIS-TERED PROFESSIONAL ARCHITECT OR ENGINEER MUST |
| CERTIFY THE DESIGN [44 CFR 60.3(C)(5)]. IF A FULL-STORY |
| ENCLOSURE IS PLANNED BELOW THE ELEVATED LOWEST FLOOR, |
| YOU SHOULD REQUIRE THE APPLICANT TO SIGN A |
| NON-CONVERSION AGREEMENT SUCH AS THE ONE IN FIGURE |
| 5-13. |
| |
| PLEASE PROVIDE BASE FLOOD ELEVATION CERTIFICATE FEMA |
| FORM 086-0-33 TO SHOW WHAT PROPOSED BASE ELEVATION IS |
| GOING TO BE. |
| ACCORDING TO THE FIRM MAP FOR WPB THE BFE IS 12.7 FEET. |
| ORDINANCE 4729-17 SEC. 18-34 REQUIRES ADDITIONAL |
| FREEBOARD OF 2 FEET, SO THE DESIGN BFE SHOULD BE 14.7 |
| (SURVEYOR TO VERIFY AND STATE ON CERTIFICATE) |
| |
| IF THE PROPOSED FLOOR IS LOWER THAN THE DESIGN BFE AND |
| THE INTENT IS TO MAINTAIN FLOOR LEVEL OF EXISTING, DRY |
| FLOOD PROOFING CAN BE DONE TO THE DESIGN BFE LEVEL. |
| DRY FLOODPROOFING WILL REQUIRE A SUBMITTAL AND THE |
| ENGINEER WILL ALSO NEED TO PROVIDE DESIGN CERTIFICATION |
| FEMA FORM 086-0-34. |
| |
| PLEASE FEEL FREE TO CALL OR E-MAIL ME ABOUT THIS |
| ANYTIME. |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| P.S. IT WOULD BE ADVISABLE TO CONTACT YOUR FLOOD |
| INSURANCE PROVIDER TO ASK ABOUT |
| ONE FOOT DEDUDCTION OF BFE FOR FLOOD PROOFING. WHEN |
| FLOOD PROOFING IS DONE INSTEAD |
| OF BRINGING THE LOWEST FLOOR ELEVATION UP TO BFE THE |
| ADJUSTER WILL TAKE OFF ONE |
| FOOT AND THIS MEANS THAT THE FLOODPROOFING WOULD NEED |
| TO BE ONE ADDITIONAL FOOT |
| TO GET THE SAME RATE AS BRINGING FLOOR UP TO BFE. |
| IN THE CASE OF ADDING FREEBOARD BEYOND THE FIRM BFE I |
| DON'T KNOW IF YOU WOULD NEED THAT |
| ADDITIONAL FOOT ON TOP OF THE ESTABLISHED DESIGN |
| ELEVATION. |