Plan Review Notes
Plan Review Notes For Permit 18090121
Permit Number 18090121
Review Stop M
Sequence Number 1
Notes
Date Text
2018-10-17 11:58:061ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090121
 10/17/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2.1: SHOW THE LOCATIONS OF THE REQUIRED DUCT
 SMOKE DETECTORS IN THE SUPPLY AIR SYSTEMS OF RTU- 1 & 2
 PER SECTION 606.2.1 FBC M, AND PROVIDE A SEQUENCE OF
 OPERATION FOR FAN SHUTDOWN AND HOW THE DEVICES WILL BE
 SUPERVISED- SECTIONS 606.4 & 606.4.1.
  
 2) M2.1: THE PLAN DOES NOT CLEARLY SHOW THE LOCATION OF
 THE TOILET ROOM EXHAUST TERMINATION- SECTION 501.3.1
 FBC M.
  
 3) M2.1 & M2.2: PROVISDE CONDENSATE DISPOSAL PLANS FOR
 THE RTU'S AND THE AHU- SECTION 307 FBC M.
  
 4) M2.2 & M6.1: PROVIDE COMPLETE WINDLOAD ENGINEERING
 FOR INSTALLATION OF THE RTU'S AND CURBS, AND FOR THE
 CONDENSER STAND ON THE ROOF- SECTION 301.15 FBC M.
 PLEASE INCLUDE THE DESIGN CRITERIA AS OUTLINED IN
 SECTION 1609 FBC M, AND SUBMIT THE NOA FOR THE STAND.
  
 5) REFER TO SECTION 306.5 FBC M AND CLARIFY HOW ACCESS
 TO THE ROOFTOP EQUIPMENT IS BEING PROVIDED.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  