2018-11-02 15:48:30 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18090121 |
| REVIEWED: NOVEMBER 1, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC ENERGY = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. ART IN PUBLIC PLACES |
| THE CITY OF WEST PALM BEACH ART IN PUBLIC PLACES |
| ORDINANCE REQUIREMENT THAT APPLIES TO ANY REMODEL OR |
| NEW CONSTRUCTION PROJECT FOR WHICH THE PERMIT |
| APPLICATION WAS SUBMITTED AFTER 6/29/14, AND THE TOTAL |
| PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR GREATER THAN |
| $750,000 WILL NEED TO COMPLY WITH THIS ORDINANCE. |
| PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND |
| CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V, |
| ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION |
| 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL |
| PROJECT CONSTRUCTION COST. |
| PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE |
| V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND |
| NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO |
| THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE |
| PROJECTS. |
| SEC. 78-129. - PUBLIC ART ASSESSMENT FOR PRIVATE |
| DEVELOPMENT. |
| (A) APPLICABILITY. THE PROVISIONS OF THIS ARTICLE AND |
| THE PUBLIC ART ASSESSMENT SECTION SHALL APPLY TO ALL |
| PRIVATE DEVELOPMENT PROJECTS, INCLUDING NEW |
| CONSTRUCTION, OR THE RENOVATION OR IMPROVEMENT OF AN |
| EXISTING BUILDING, WHERE TOTAL CONSTRUCTION COSTS ARE |
| EQUAL TO OR GREATER THAN $750,000.00. ALL BUILDINGS |
| WITHIN NEW PLANNED DEVELOPMENTS SHALL BE ASSESSED |
| CUMULATIVELY TOWARDS THIS ART IN PUBLIC PLACES |
| REQUIREMENT, EVEN IF THE BUILDINGS ARE PERMITTED |
| SEPARATELY OR DEVELOPED IN PHASES. THE PROVISIONS OF |
| THIS SECTION APPLY TO NEW DEVELOPMENT OR NEW |
| CONSTRUCTION WITHIN EXISTING PLANNED DEVELOPMENTS. |
| FOR CONTACT INFORMATION PLEASE CONTACT: |
| MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR |
| 822-1515 E-MAIL: [email protected] |
| |
| 2. [FBC AMENDED 107.3.5.1.1]PROVIDE BASE FLOOD |
| ELEVATION(B.F.E.) CERTIFICATE WITH DESIGN FLOOD |
| ELEVATIONS TO INCLUDE ANY MECHANICAL EQUIPMENT AS |
| APPLICABLE. ALL ELEVATION CERTIFICATES CERTIFIED |
| OCTOBER 5, 2017 AND LATER ARE TO UTILIZE NAVD88 AND |
| INCLUDE A CONVERSION TO NGVD29. |
| |
| 3. [ORDINANCE NO. 4658-16][WPB MUNI CODE SEC. 18-33] |
| TECHNICAL AMENDMENTS TO FLORIDA BUILDING CODE, |
| RESIDENTIAL. BUILDINGS AND STRUCTURES IN FLOOD HAZARD |
| AREAS DESIGNATED AS COASTAL A ZONES SHALL HAVE THE |
| LOWEST FLOORS ELEVATED TO OR ABOVE THE BASE FLOOD |
| ELEVATION PLUS TWO FEET OR THE DESIGN FLOOD ELEVATION, |
| WHICHEVER IS HIGHER. |
| |
| 4. [FBC 401.4]PROVIDE SOIL REPORT TO SHOW BEARING |
| CAPACITY AND FOUNDATION RECOMMENDATIONS. UPLOAD INTO |
| SUPPORTING FILES. |
| |
| 5. [FBC 107.2.5]PROVIDE SURVEY OF PROPERTY SHOWING |
| EASEMENTS. UPLOAD INTO SUPPORTING FILES. |
| |
| 6. [FBC 107.3.5.3]UPDATE CODE REFERENCES ON SHEET A0-01 |
| ADOPTED DECEMBER 31, 2017 |
| BUILDING, ENERGY, MECHANICAL PLUMBING, ACCESSIBILITY |
| FLORIDA BUILDING CODE(FBC), 6TH EDITION (2017) |
| FLORIDA FIRE PREVENTION, 6TH EDITION |
| |
| 7. [FBC AMENDED107.3.5]SHEET A0-01 PROJECT INFO DOESN?T |
| MATCH LIFE SAFETY SHEET. IF THIS IS EXISTING BUILDING |
| DATA PLEASE LABLE AS SUCH, OR MATCH WITH DATA ON LIFE |
| SAFETY SHEET. |
| WHAT IS THE EXISTING OCCUPANCY(S) OF THE 21,008 SQ. FT. |
| SPACE? |
| HOW MANY OCCUPANTS? |
| |
| 8. [FBC 718]HOW ARE THE CONCEALED SPACES HANDLED |
| BETWEEN EXISTING AND NEW AT ROLL UP DOOR 006? |
| |
| 9. [FBC 1907.1]SHEET A3.11 AND A3.12 STATE 4" CONCRETE |
| SLAB, BUT STRUCTURAL SHOWS 5" SLAB. PLEASE CO-ORDINATE |
| THE ARCHITECTURAL AND STRUCTURAL DRAWINGS TO MATCH. |
| SHEET A0-02 WHY EGRESS INTO EXISTING SPACE? IF THAT |
| WILL BE AN EGRESS THAN SHOW HOW IT PROVIDE EGRESS TO |
| THE PUBLIC RIGHT OF WAY FROM DOOR 003. |
| |
| 10. [FBC A604.5.1] THE SIDE WALL GRAB BAR SHALL BE 42 |
| INCHES (1065 MM) LONG MINIMUM, LOCATED 12 INCHES (305 |
| MM) MAXIMUM FROM THE REAR WALL AND EXTENDING 54 INCHES |
| (1370 MM) MINIMUM FROM THE REAR WALL. |
| [FBC A604.5.2] THE REAR WALL GRAB BAR SHALL BE 36 |
| INCHES (915 MM) LONG MINIMUM AND EXTEND FROM THE |
| CENTERLINE OF THE WATER CLOSET 12 INCHES (305 MM) |
| MINIMUM ON ONE SIDE AND 24 INCHES (610 MM) MINIMUM ON |
| THE OTHER SIDE. |
| ADJUST NOTES ON A4.11 (DETAIL 1) TO STATE PROPER LENGTH |
| OF GRAB BARS IN RESTROOMS. GRAPHICLLY THEY APPEAR |
| CORRECT SIZE. |
| SHOW LENGTH OF BACK GRAB BARS IN RESTROOMS |
| |
| 11. [FBC AMENDED 107.3.5]THE ADA PARKING APPEARS TO BE |
| IN THE RIGHT OF WAY. |
| CONTACT ENGINEERING (561-494-1040) FOR PERMIT THAT |
| PERTAINS TO THE R.O.W. |
| PROVIDE PARKING DATA TO MEET REQUIREMENTS FOR ADA AND |
| NEW SPACES REQUIRED. |
| |
| 12. [FBC 1510.10]ROOF MOUNTED MECHANICAL UNITS SHALL BE |
| MOUNTED ON CURBS RAISED A MINIMUM OF 8 INCHES (203 MM) |
| ABOVE THE ROOF SURFACE, OR WHERE ROOFING MATERIALS |
| EXTEND BENEATH THE UNIT, ON RAISED EQUIPMENT SUPPORTS |
| PROVIDING A MINIMUM CLEARANCE HEIGHT IN ACCORDANCE WITH |
| TABLE 1510.10. |
| PROVIDE STRUCTURAL DETAIL OF ROOF CURB. |
| |
| 13. [FBC 1503.4]ROOF DRAINAGE |
| PROVIDE ROOF DRAIN CALCULATIONS AND DESIGN TO COMPLY |
| WITH SECTIONS 1106 AND 1107, AS APPLICABLE, OF THE |
| FLORIDA BUILDING CODE, PLUMBING, CHAPTER 11. |
| |
| 14. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS |
| FOR ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM |
| DEFERED. |
| |
| 15. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS |
| FOR WINDOWS, DOORS, ROLL-UP DOOR AND STOREFRONT, OR |
| INDICATE THAT YOU WOULD LIKE THEM DEFERED. |
| |
| NOTE: |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |