2018-10-04 12:54:52THE FOLLOWING ITEMS ARE PROVISOS AND MUST BE ADDRESSED
 BEFORE ANY FINAL INSPECTIONS ARE SCHEDULED FOR ANY OF
 THESE SYSTEMS.
  
 SUBMIT A DETAIL OF THE CONDENSATE DRYWELL FOR REVIEW.
 2017 FBC SEC. 107.2.1.
 SHT. P-102 - SHOW THE SQUARE FOOT AREA OF THE ROOF OF
 THE PORTE COCHERES BEING DRAINED. INCLUDE ONE-HALF OF
 THE AREA OF ANY PARAPET WALLS. 2017 FPC SEC.1106.4.
 SUBMIT SPECIFICATIONS FOR THE COMBO ROOF DRAINS.
 SHT. P-101. CLOUD AND IDENTIFY THE CHANGES MADE TO THE
 PLUMBING SYSTEM. CURRENTLY, THERE ARE NO CHANGES SHOWN
 ON THIS SHEET. CLARIFY.
 SUBMIT REVISED PIPING RISERS FOR THE SANITARY, STORM,
 AND CONDENSATE SYSTEMS THAT CLEARLY REFLECT ALL THE
 CHANGES MADE TO THESE SYSTEMS. SHOW THE LINT TRAP ON
 THE RISER AND SUBMIT A DETAIL OF THE LINT TRAP. FBC
 107.2.1.
 SUBMIT A REVISED GAS RISER WITH THE CORRECT PIPE
 SIZING.
  
 SPECIFICATION SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE
 WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2014 FUEL GAS SEC. 301.3.
  
 LOCATION, LENGTH, SIZE AND
 TERMINATION OF THE GAS VENTS PER
 FBC-2014 FUEL GAS CODE SEC. 502 THRU
 504. SUBMIT CALCULATIONS FOR
 COMBUSTION AIR PER THE FBC-2014
 FUEL GAS CODE SEC. 304. FOR BOILERS
  
 COMBUSTION AIR PER THE FBC-2014
 FUEL GAS CODE SEC. 304. FOR BOILER
 AND DRYERS
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW