Plan Review Notes
Plan Review Notes For Permit 18090102
Permit Number 18090102
Review Stop M
Sequence Number 1
Notes
Date Text
2018-09-25 15:25:34MECHANICAL PROVISOS:
 REVISION #18090102
 MASTER #18020252
 10/4/18
  
 1) SHEET M103, 3RD-9TH FLOORS: PROVIDE FIRE DAMPERS FOR
 THE 12X12 AND !2X10 SUPPLY DUCTS PENETRATING THE
 FIRE-RATED CORRIDOR WALLS- SECTION 607.5.3 FBC M.
  
 2) ACCORDING TO THE NARRATIVE SUBMITTED WITH THE
 REVISED PLANS, THERE ARE CHANGES TO THE DUCTWORK ON THE
 10TH FLOOR (SHEET M104), HOWEVER THE REVISED PLAN WAS
 NOT UPLOADED FOR REVIEW. PLEASE PROVIDE THE PLAN.
  
 3) M106: THERE IS NO CODE REQUIREMENT FOR SMOKE
 DETECTORS TO BE LOCATED BY THE STAIR PRESSURIZATION
 FANS IN THE INTERIOR EXIT STAIRWAYS. PLEASE PROVIDE A
 RATIONAL ANALYSIS TO CLARIFY THE FUNCTION AND CONTROLS
 OPERATION OF THE DEVICES, AND HOW THEY WILL BE
 SUPERVISED.
  
 4) M106: PROVIDE FIRE-RATED DUCTS FOR THE ELEVATOR
 PRESSURIZATION FAN SYSTEMS- SECTION 909.21.3 FBC B.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  