Notes |
Date |
Text |
2018-09-25 15:25:34 | MECHANICAL PROVISOS: | | REVISION #18090102 | | MASTER #18020252 | | 10/4/18 | | | | 1) SHEET M103, 3RD-9TH FLOORS: PROVIDE FIRE DAMPERS FOR | | THE 12X12 AND !2X10 SUPPLY DUCTS PENETRATING THE | | FIRE-RATED CORRIDOR WALLS- SECTION 607.5.3 FBC M. | | | | 2) ACCORDING TO THE NARRATIVE SUBMITTED WITH THE | | REVISED PLANS, THERE ARE CHANGES TO THE DUCTWORK ON THE | | 10TH FLOOR (SHEET M104), HOWEVER THE REVISED PLAN WAS | | NOT UPLOADED FOR REVIEW. PLEASE PROVIDE THE PLAN. | | | | 3) M106: THERE IS NO CODE REQUIREMENT FOR SMOKE | | DETECTORS TO BE LOCATED BY THE STAIR PRESSURIZATION | | FANS IN THE INTERIOR EXIT STAIRWAYS. PLEASE PROVIDE A | | RATIONAL ANALYSIS TO CLARIFY THE FUNCTION AND CONTROLS | | OPERATION OF THE DEVICES, AND HOW THEY WILL BE | | SUPERVISED. | | | | 4) M106: PROVIDE FIRE-RATED DUCTS FOR THE ELEVATOR | | PRESSURIZATION FAN SYSTEMS- SECTION 909.21.3 FBC B. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|