Plan Review Notes
Plan Review Notes For Permit 18090013
Permit Number 18090013
Review Stop M
Sequence Number 1
Notes
Date Text
2018-10-12 12:10:381ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18090013
 10/12/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M1.1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY AIR SYSTEMS OF EACH 5-TON RTU SYSTEM PER SECTION
 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED
 IF THE MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS
 ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY
 AIR. PLEASE PROVIDE SYMBOLS ON THE PLAN TO INDICATE
 INDICATE THE DEVICE LOCATIONS.
  
 2) PROVIDE NOTES ON THE PLAN TO INDICATE THE FAN
 SHUTDOWN SEQUENCE AND HOW THE DETECTORS WILL BE
 SUPERVISED- SECTIONS 606.4 & 606.4.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  