2018-10-12 12:10:38 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18090013 |
| 10/12/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M1.1: DUCT SMOKE DETECTORS ARE REQUIRED IN THE |
| SUPPLY AIR SYSTEMS OF EACH 5-TON RTU SYSTEM PER SECTION |
| 606.2.1. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED |
| IF THE MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS |
| ARE NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY |
| AIR. PLEASE PROVIDE SYMBOLS ON THE PLAN TO INDICATE |
| INDICATE THE DEVICE LOCATIONS. |
| |
| 2) PROVIDE NOTES ON THE PLAN TO INDICATE THE FAN |
| SHUTDOWN SEQUENCE AND HOW THE DETECTORS WILL BE |
| SUPERVISED- SECTIONS 606.4 & 606.4.1 FBC M. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |