2018-11-01 16:50:07 | ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. THE APPLICATION AND SHT. A-0.01 UNDER SCOPE OF WORK |
| STATE A CHANGE OF OCCUPANCY FROM A STORAGE TO ASSEMBLY |
| A-2 THE PLUMBING PLAN SHALL COMPLY WITH THE A-2 FIXTURE |
| COUNT AND THE REQUIREMENT FOR SEPARATE FACILITIES, |
| THERE ARE SOME SHEETS THAT CALL OUT A BUSINESS |
| OCCUPANCY THIS SHALL BE CLARIFIED. IF IT IS YOUR INTENT |
| TO BUILD A VANILLA SHELL WITH NO OCCUPANCY REQUIREMENTS |
| THE PLAN AND THE APPLICATION WILL NEED TO SHOW THIS. |
| PER WPB AMEND TO FBC 107.2.1 AND FBC PL TABLE 403.1 AND |
| 403.2 SEPARATE FACILITIES. WHERE PLUMBING FIXTURES ARE |
| REQUIRED, SEPARATE FACILITIES SHALL BE PROVIDED FOR |
| EACH SEX. |
| 2. THE PLUMBING PLANS INCLUDE FIXTURES COMPLIANCE WITH |
| ACCESSIBILITY IS REQUIRED PLEASE PROVIDE DETAILS |
| SHOWING COMPLIANCE WITH FBC ACC 603, 604.2, 604.3.1, |
| 604.4, 604.5.1, 604.5.2, 604.7, 606.2, 606.3, 609.4 |
| 3. SHT. P-1 THE MOP SINK ON THE GROUND FLOOR SHALL |
| CONNECT DOWNSTREAM OF THE BATHROOM GROUP. PER FBC PL |
| 912.1 |
| 4. SHT. P-1 THE DRY VENT ON THE GROUND FLOOR SHALL NOT |
| RUN HORIZONTAL. PER FBC PL 905.3, 905.4, 905.5 |
| 5. SHT. P-1 THE MOP SINK ON THE 2ND AND 3RD FLOOR SHALL |
| HAVE A SEPARATE VENT. . PER FBC PL 901.2.1, 912.1 |
| 6. IF THIS IS GOING TO BE AN R-2 SERVING FOOD IT SHALL |
| HAVE A GREASE INTERCEPTOR. PER FBC PL 1003.3.1 |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |