2018-11-01 16:50:07ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE APPLICATION AND SHT. A-0.01 UNDER SCOPE OF WORK
 STATE A CHANGE OF OCCUPANCY FROM A STORAGE TO ASSEMBLY
 A-2 THE PLUMBING PLAN SHALL COMPLY WITH THE A-2 FIXTURE
 COUNT AND THE REQUIREMENT FOR SEPARATE FACILITIES,
 THERE ARE SOME SHEETS THAT CALL OUT A BUSINESS
 OCCUPANCY THIS SHALL BE CLARIFIED. IF IT IS YOUR INTENT
 TO BUILD A VANILLA SHELL WITH NO OCCUPANCY REQUIREMENTS
 THE PLAN AND THE APPLICATION WILL NEED TO SHOW THIS.
 PER WPB AMEND TO FBC 107.2.1 AND FBC PL TABLE 403.1 AND
 403.2 SEPARATE FACILITIES. WHERE PLUMBING FIXTURES ARE
 REQUIRED, SEPARATE FACILITIES SHALL BE PROVIDED FOR
 EACH SEX.
 2. THE PLUMBING PLANS INCLUDE FIXTURES COMPLIANCE WITH
 ACCESSIBILITY IS REQUIRED PLEASE PROVIDE DETAILS
 SHOWING COMPLIANCE WITH FBC ACC 603, 604.2, 604.3.1,
 604.4, 604.5.1, 604.5.2, 604.7, 606.2, 606.3, 609.4
 3. SHT. P-1 THE MOP SINK ON THE GROUND FLOOR SHALL
 CONNECT DOWNSTREAM OF THE BATHROOM GROUP. PER FBC PL
 912.1
 4. SHT. P-1 THE DRY VENT ON THE GROUND FLOOR SHALL NOT
 RUN HORIZONTAL. PER FBC PL 905.3, 905.4, 905.5
 5. SHT. P-1 THE MOP SINK ON THE 2ND AND 3RD FLOOR SHALL
 HAVE A SEPARATE VENT. . PER FBC PL 901.2.1, 912.1
 6. IF THIS IS GOING TO BE AN R-2 SERVING FOOD IT SHALL
 HAVE A GREASE INTERCEPTOR. PER FBC PL 1003.3.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  