2018-10-23 16:06:58 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18081353 |
| 10/23/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE |
| NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC. |
| |
| 2) REFER TO SECTION C505.1 FBC-17 ENERGY CONSERVATION |
| AND SUBMIT AN ENERGY EFFICIENCY COMPLIANCE REPORT FOR |
| THE CHANGE IN OCCUPANCY FROM S1 TO A2. |
| |
| 3) SHEET M-1: PLEASE PROVIDE A MORE SPECIFIC OCCUPANCY |
| CLASSIFICATION IN THE VENTILATION SCHEDULE FOR THE MAIN |
| ROOMS- TABLE 403.3.1.1 FBC M. |
| |
| 4) M-2: THE SUPPLY AIR DUCTS PENETRATING THE INTERIOR |
| EXIT STAIRWAY ARE PROHIBITED PER SECTIONS 1023.5 & |
| 1023.6 FBC B. |
| |
| 5) M-2: DUCT SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY |
| AIR SYSTEMS OF EACH 5-TON AC SYSTEM PER SECTION 606.2.1 |
| FBC M. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF |
| THE MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE |
| NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |