Plan Review Notes
Plan Review Notes For Permit 18081583
Permit Number 18081583
Review Stop M
Sequence Number 1
Notes
Date Text
2018-10-23 16:06:581ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18081353
 10/23/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEMS IN ACCORDANCE WITH SECTION C403.2.1 FBC EC.
  
 2) REFER TO SECTION C505.1 FBC-17 ENERGY CONSERVATION
 AND SUBMIT AN ENERGY EFFICIENCY COMPLIANCE REPORT FOR
 THE CHANGE IN OCCUPANCY FROM S1 TO A2.
  
 3) SHEET M-1: PLEASE PROVIDE A MORE SPECIFIC OCCUPANCY
 CLASSIFICATION IN THE VENTILATION SCHEDULE FOR THE MAIN
 ROOMS- TABLE 403.3.1.1 FBC M.
  
 4) M-2: THE SUPPLY AIR DUCTS PENETRATING THE INTERIOR
 EXIT STAIRWAY ARE PROHIBITED PER SECTIONS 1023.5 &
 1023.6 FBC B.
  
 5) M-2: DUCT SMOKE DETECTORS ARE REQUIRED IN THE SUPPLY
 AIR SYSTEMS OF EACH 5-TON AC SYSTEM PER SECTION 606.2.1
 FBC M. PLEASE NOTE THAT AN EXEMPTION CAN BE APPLIED IF
 THE MANUFACTURER'S SPECIFICATIONS INDICATE SYSTEMS ARE
 NOT CAPABLE OF PRODUCING OVER 2000 CFMS OF SUPPLY AIR.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  