Plan Review Notes
Plan Review Notes For Permit 18081583
Permit Number 18081583
Review Stop E
Sequence Number 1
Notes
Date Text
2018-10-11 15:52:46CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE MORE DETAIL FOR WIRE AND CONDUIT SIZES. AS
 AN EXAMPLE, THE OVERHEAD RISER SHOWS (3) 400 MCM IN 3
 INCH CONDUIT. THIS WOULD NOT EQUAL THE NUMBER OR SIZE
 OF WIRES REQUIRED FOR A 120/208, 3 PHASE, 1000 AMP
 SERVICE. ADDITIONALLY, PROVIDE WIRE AND CONDUIT SIZES
 FOR EACH PORTION OF THE FEEDER WIRES AND TAPS TO
 DETERMINE CODE COMPLIANCE. WPB FBC 107.2.1; NEC 240.21,
 310.15(B)(16)
 2. RISER DIAGRAM SHOWS PANEL 1, 2, AND 3. PANEL
 SCHEDULES PROVIDED SHOW PANEL 1, 2, AND HP. PROVIDE
 CLARIFICATION AND CORRECTION. WPB FBC 107.2.1
 3. LOCATION OF SERVICE DISCONNECTS AND METERS ARE NOT
 SHOWN ON PLAN. PROVIDE CORRECTION. WPB FBC 107.2.1
 4. RISER DIAGRAM SHOWS A 400 AMP METER FEEDING PANEL 1
 WITH NO DISCONNECT/OVERCURRENT PROTECTION FOR THE
 CONDUCTORS. WHAT IS THE DISTANCE OF THIS WIRE RUN AND
 WHICH TAP RULE WILL APPLY? PROVIDE CLARIFICATION AND/OR
 CORRECTION. NEC 240.21; WPB FBC 107.2.1
 5. IT APPEARS THIS PROJECT IS FOR SHELL ONLY. PROVIDE
 JUSTIFICATION FOR SERVICE SIZE. HOW IS THE LOAD
 DETERMINED? NEC 220; WPB FBC 107.2.1
 6. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND
 VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS
 IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD
 SHEETS.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved