Plan Review Notes
Plan Review Notes For Permit 18081583
Permit Number 18081583
Review Stop B
Sequence Number 1
Notes
Date Text
2018-11-14 08:54:08****CORRECTIONS****
 W.P.B. PERMIT: 18081583
 REVIEWED: NOVEMBER 14, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
  
 1. [FBC ENERGY C503.1]GENERAL. ALTERATIONS TO ANY
 BUILDING OR STRUCTURE
 SHALL COMPLY WITH THE REQUIREMENTS OF THE CODE FOR NEW
 CONSTRUCTION.
 PROVIDE DOCUMENTATION SUCH AS FORM C402-2017 TO SHOW
 COMPLIANCE
  
 2. [FBC TABLE 705.8]MAXIMUM AREA OF EXTERIOR WALL
 OPENINGS BASED ON FIRE SEPARATION DISTANCE AND DEGREE
 OF OPENING PROTECTION. PROVIDE SITE PLAN OR SURVEY TO
 SHOW SEPARATION FORM ADJACENT BUILDINGS.
  
 3. [FBC 1004.1]HOW WAS OCCUPANT LOAD DECREASED FOR A-2
 AREA? A REDUCTION MAY BE REQUESTED TO THE BUILDING
 OFFICIAL, BUT IT WOULD HAVE JUSTIFICATION THAT THE SOME
 AREA WAS NOT USABLE DUE TO REASONS YOU WOULD STATE.
 PLEASE ADJUST YOUR OCCUPANCY FOR THE FULL USE OF THE
 BUILDING AND INCLUDE THE OUTSIDE EATING AREA AS WELL.
 ROOF TOP DINING NEEDS TO SHOW HOW SPACE KEEPS OCCUPANTS
 WITHIN THE AREA DEFINED. PERMANENT GUARDRAILS OR
 SIMILAR PERMANENT STRUCTURE.
  
 4. [FBC A202.3]ALTERATIONS. WHERE EXISTING ELEMENTS OR
 SPACES OR COMMON AREAS ARE ALTERED, EACH ALTERED
 ELEMENT,
 SPACE OR AREA SHALL COMPLY WITH THE APPLICABLE
 REQUIREMENTS OF CHAPTER 2 AND SECTION 201.1.1.
 IF USING 202.4.1 DIPORPORTIONATE COST TO EXEMPT ACCESS
 TO OUTDOOR SEATING, USE VALUATION OF SHELL WORK PLUS
 BUILD OUT TO DETERMINE THE 20% VALUE OF PROMARY
 FUNCTION.
  
 5. [FBC A404.2.6]DOORS IN SERIES AND GATES IN SERIES.
 THE DISTANCE BETWEEN TWO HINGED OR PIVOTED DOORS IN
 SERIES AND GATES IN SERIES SHALL BE 48 INCHES (1220 MM)
 MINIMUM PLUS THE WIDTH OF DOORS OR GATES SWINGING INTO
 THE SPACE.
 CHECK DISTANCE BETWEEN EXIT DOOR 103 TO MAIN EXIT 101
 FOR 48 INCHES CLEAR WHEN DOOR 103 IS IN THE OPEN
 POSITION.
  
 6. [FBC 107.3.5]SHEET A-1.02 CALLS OUT SECTION 2/4.01,
 BUT IT IS SECTION A-A. PLEASE MATCH DETAIL CALL-OUT TO
 SECTION IT REFERS.
  
 7. [FBC 107.3.5]SEE SECTION 208.1 FOR EXISTING
 PARKING.SHEET A-0.01 IN CODE ANALYSIS EXISTING BLDG
 CLASS, CHANGE CODE REFERENCE TO FBC 2017 6TH EDITION.
  
 8. [FBC AMENDED 107.3.4.1]PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, WINDOW MULL, STOREFRONT AND DOORS, OR INDICATE
 THAT YOU WOULD LIKE THEM DEFERED.
  
 9. [FBC AMENDED 107.2.1.2]PROVIDE METAL PAN STAIRCASE
 ENGINEERING, OR INDICATE THAT IT WILL BE A DEFERRED
 SUBMITTAL.
  
 10. [FBC AMENDED 107.2.1.2]GUARD RAIL ENGINEERING, OR
 INDICATE THAT IT WILL BE DEFERRED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  