2018-11-14 12:37:44 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHT. A-400 THE ADA BATHROOM SHALL COMPLY WITH FBC |
| ACC |
| 604.7 DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY |
| WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES |
| MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE |
| CENTERLINE OF THE DISPENSER. |
| 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE |
| 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE |
| WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM |
| THE REAR WALL. |
| 604.2 LOCATION.THE WATER CLOSET SHALL BE POSITIONED |
| WITH A WALL OR PARTITION TO THE REAR AND TO ONE SIDE. |
| THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES |
| MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR |
| PARTITION |
| |
| 2. THE REVISION NARRATIVE LIST SHT. A-4.18 IT IS NOT |
| INCLUDED IN PLAN SHEETS SUBMITTED/. PLEASE CLARIFY WPB |
| AMEND TO FBC 107.2.1 |
| |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |