Plan Review Notes
Plan Review Notes For Permit 18081535
Permit Number 18081535
Review Stop P
Sequence Number 1
Notes
Date Text
2018-11-14 12:37:441ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A-400 THE ADA BATHROOM SHALL COMPLY WITH FBC
 ACC
 604.7 DISPENSERS. TOILET PAPER DISPENSERS SHALL COMPLY
 WITH 309.4 AND SHALL BE 7 INCHES MINIMUM AND 9 INCHES
 MAXIMUM IN FRONT OF THE WATER CLOSET MEASURED TO THE
 CENTERLINE OF THE DISPENSER.
 604.3.1 SIZE. CLEARANCE AROUND A WATER CLOSET SHALL BE
 60 INCHES MINIMUM MEASURED PERPENDICULAR FROM THE SIDE
 WALL AND 56 INCHES MINIMUM MEASURED PERPENDICULAR FROM
 THE REAR WALL.
 604.2 LOCATION.THE WATER CLOSET SHALL BE POSITIONED
 WITH A WALL OR PARTITION TO THE REAR AND TO ONE SIDE.
 THE CENTERLINE OF THE WATER CLOSET SHALL BE 16 INCHES
 MINIMUM TO 18 INCHES MAXIMUM FROM THE SIDE WALL OR
 PARTITION
  
 2. THE REVISION NARRATIVE LIST SHT. A-4.18 IT IS NOT
 INCLUDED IN PLAN SHEETS SUBMITTED/. PLEASE CLARIFY WPB
 AMEND TO FBC 107.2.1
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  