2018-10-04 18:55:33 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| REVISION IS DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THERE ARE SHEETS LISTED IN THE NARRATIVE DESCRIPTION |
| OF DRAWING REVISIONS THAT ARE MISSING FROM DRAWINGS |
| THAT WERE UPLOADED. SHEET LS-111A, SHEET A-3.04 AND |
| SHEETS A-4.00 THROUGH A-6.06 ARE MISSING FROM THE |
| DRAWINGS. PLEASE CLARIFY. FBC 107.2.1 |
| |
| 2) SHEET A-1101 IS ONE OF THE DRAWINGS UPLOADED AND IT |
| IS NOT LISTED IN THE REVISION NARRATIVE. FBC 107.2.1 |
| |
| 3) SHEET LS-1.21 AND LS-1.31 SPECIFY THAT PRE-FUNCTION |
| ROOM 227 AND THE EXIT VESTIBULES AT THE EGRESS STAIRS |
| ARE DESIGNATED AS AN AREA OF REFUGE. THE SECTIONS FOR |
| AREAS OF REFUGE WAS NOT ADOPTED INTO THE 2017 FLORIDA |
| BUILDING CODE FROM THE 2015 INTERNATIONAL BUILDING |
| CODE. SECTION 1009.6 AREAS OF REFUGE IS RESERVED. IT IS |
| GOOD THAT THESE AREAS HAVE SMOKE BARRIERS. HOWEVER, |
| THEY SHOULD NOT BE DESIGNATED AS AREAS OF REFUGE AS |
| THEY ARE NOT RECOGNIZED BY THE FBC AND THE REQUIREMENTS |
| FOR THEM ARE NOT CODIFIED. |
| |
| 4) SHEETS A-3.04 SPECIFIES AN APPLIED FOAM MOLDING WITH |
| STUCCO FINISH ATTACHED TO THE PARAPET. PROVIDE A DETAIL |
| SHOWING MATERIALS, THICKNESSES AND ATTACHMENT METHOD. |
| FOAM PLASTIC IS NOT ALLOWED ON THE EXTERIOR WALLS OF |
| BUILDINGS OF TYPE I OR TYPE II CONSTRUCTION UNLESS IT |
| MEETS THE REQUIREMENTS OF FBC 2603.5.1 THROUGH 2603.5.7 |
| |
| 5) PRODUCT APPROVALS AND ATTACHMENT/ FASTENING DETAILS |
| WILL BE REQUIRED FOR THE STONE CLADDING. |
| |
| 6) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE |
| CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |