2018-09-04 16:15:01 | THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC, |
| FIRE MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| PLEASE CONSIDER THE FOLLOWING AS PROVISO: |
| |
| THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED |
| AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE |
| PROVISO COMMENTS WILL RESULT IN A FAILED FIRE |
| INSPECTION. |
| |
| |
| |
| 1) THERE ARE INDICATIONS THAT SMOKE DETECTORS SHALL |
| CAUSE A FULL ALARM. DUCT DETECTORS SHALL BE PROGRAM TO |
| CAUSE A SUPERVISORY SIGNAL. |
| |
| |
| PER 2015 NFPA 90A |
| |
| 6.4.3* FUNCTION. |
| 6.4.3.1 SMOKE DETECTORS PROVIDED AS REQUIRED BY 6.4.2 |
| SHALL AUTOMATICALLY STOP THEIR RESPECTIVE FAN(S) ON |
| DETECTING THE PRESENCE OF SMOKE. |
| |
| 6.4.4.2 IN ADDITION TO THE REQUIREMENTS OF 6.4.3, WHERE |
| AN APPROVED FIRE ALARM SYSTEM IS INSTALLED IN A |
| BUILDING, THE SMOKE DETECTORS REQUIRED BY THE |
| PROVISIONS OF SECTION 6.4 SHALL BE CONNECTED TO THE |
| FIRE ALARM SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS |
| OF NFPA 72, NATIONAL FIRE ALARM AND SIGNALING |
| CODE. |
| |
| 6.4.4.2.1 SMOKE DETECTORS USED SOLELY FOR CLOSING |
| DAMPERS OR FOR HEATING, VENTILATING, AND |
| AIR-CONDITIONING SYSTEM SHUTDOWN SHALL NOT BE REQUIRED |
| TO ACTIVATE THE BUILDING EVACUATION ALARM. |
| |
| 6.4.4.3 WHERE SMOKE DETECTORS REQUIRED BY SECTION 6.4 |
| ARE INSTALLED IN A BUILDING NOT EQUIPPED WITH AN |
| APPROVED FIRE ALARM SYSTEM AS SPECIFIED BY 6.4.4.2, THE |
| FOLLOWING SHALL OCCUR: |
| (1) SMOKE DETECTOR ACTIVATION REQUIRED BY SECTION 6.4 |
| SHALL CAUSE A VISUAL SIGNAL AND AN AUDIBLE SIGNAL IN A |
| NORMALLY OCCUPIED AREA. |
| (2) SMOKE DETECTOR TROUBLE CONDITIONS SHALL BE |
| INDICATED VISUALLY OR AUDIBLY IN A NORMALLY OCCUPIED |
| AREA AND SHALL BE IDENTIFIED AS AIR DUCT DETECTOR |
| TROUBLE. |
| |
| AND |
| |
| NFPA 72 |
| |
| 23.8.5.4.6 SIGNAL INITIATION ? DUCT SMOKE DETECTORS. |
| 23.8.5.4.6.1 WHERE DUCT SMOKE DETECTORS ARE REQUIRED TO |
| BE |
| MONITORED AND A BUILDING FIRE ALARM SYSTEM IS |
| INSTALLED, A DUCT |
| DETECTOR ACTIVATION SIGNAL SHALL MEET THE REQUIREMENTS |
| OF 21.7.4. |
| 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC |
| SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL. |
| 21.7.4.1 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF |
| HVAC |
| SYSTEMS IN A FIRE ALARM SYSTEM WITHOUT A CONSTANTLY |
| ATTENDED |
| LOCATION OR SUPERVISING STATION SHALL BE PERMITTED TO |
| INITIATE AN |
| ALARM SIGNAL. |
| 21.7.4.2 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF |
| HVAC |
| SYSTEMS SHALL BE PERMITTED TO INITIATE AN ALARM SIGNAL |
| WHERE |
| REQUIRED BY OTHER GOVERNING LAWS, CODES, OR STANDARDS. |
| |
| |
| PLEASE PROGRAM THE DUCT DETECTORS TO CAUSE A |
| SUPERVISSORY SIGNAL PER THE APPLICABLE CODES. |
| |
| |
| PETER LEDUC |
| FIRE MARSHAL |
| 561-804-4709 |
| [email protected] |
| |
| |