Plan Review Notes
Plan Review Notes For Permit 18081513
Permit Number 18081513
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-09-04 16:15:01THIS PLAN WAS REVIEWED AND APPROVED BY PETER LEDUC,
 FIRE MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 PLEASE CONSIDER THE FOLLOWING AS PROVISO:
  
 THESE PROVISO COMMENTS WILL BE VERIFIED AND CONFIRMED
 AT THE TIME OF FIRE INSPECTION. FAILURE TO FOLLOW THESE
 PROVISO COMMENTS WILL RESULT IN A FAILED FIRE
 INSPECTION.
  
  
  
 1) THERE ARE INDICATIONS THAT SMOKE DETECTORS SHALL
 CAUSE A FULL ALARM. DUCT DETECTORS SHALL BE PROGRAM TO
 CAUSE A SUPERVISORY SIGNAL.
  
  
 PER 2015 NFPA 90A
  
 6.4.3* FUNCTION.
 6.4.3.1 SMOKE DETECTORS PROVIDED AS REQUIRED BY 6.4.2
 SHALL AUTOMATICALLY STOP THEIR RESPECTIVE FAN(S) ON
 DETECTING THE PRESENCE OF SMOKE.
  
 6.4.4.2 IN ADDITION TO THE REQUIREMENTS OF 6.4.3, WHERE
 AN APPROVED FIRE ALARM SYSTEM IS INSTALLED IN A
 BUILDING, THE SMOKE DETECTORS REQUIRED BY THE
 PROVISIONS OF SECTION 6.4 SHALL BE CONNECTED TO THE
 FIRE ALARM SYSTEM IN ACCORDANCE WITH THE REQUIREMENTS
 OF NFPA 72, NATIONAL FIRE ALARM AND SIGNALING
 CODE.
  
 6.4.4.2.1 SMOKE DETECTORS USED SOLELY FOR CLOSING
 DAMPERS OR FOR HEATING, VENTILATING, AND
 AIR-CONDITIONING SYSTEM SHUTDOWN SHALL NOT BE REQUIRED
 TO ACTIVATE THE BUILDING EVACUATION ALARM.
  
 6.4.4.3 WHERE SMOKE DETECTORS REQUIRED BY SECTION 6.4
 ARE INSTALLED IN A BUILDING NOT EQUIPPED WITH AN
 APPROVED FIRE ALARM SYSTEM AS SPECIFIED BY 6.4.4.2, THE
 FOLLOWING SHALL OCCUR:
 (1) SMOKE DETECTOR ACTIVATION REQUIRED BY SECTION 6.4
 SHALL CAUSE A VISUAL SIGNAL AND AN AUDIBLE SIGNAL IN A
 NORMALLY OCCUPIED AREA.
 (2) SMOKE DETECTOR TROUBLE CONDITIONS SHALL BE
 INDICATED VISUALLY OR AUDIBLY IN A NORMALLY OCCUPIED
 AREA AND SHALL BE IDENTIFIED AS AIR DUCT DETECTOR
 TROUBLE.
  
 AND
  
 NFPA 72
  
 23.8.5.4.6 SIGNAL INITIATION ? DUCT SMOKE DETECTORS.
 23.8.5.4.6.1 WHERE DUCT SMOKE DETECTORS ARE REQUIRED TO
 BE
 MONITORED AND A BUILDING FIRE ALARM SYSTEM IS
 INSTALLED, A DUCT
 DETECTOR ACTIVATION SIGNAL SHALL MEET THE REQUIREMENTS
 OF 21.7.4.
 21.7.4 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF HVAC
 SYSTEMS SHALL INITIATE A SUPERVISORY SIGNAL.
 21.7.4.1 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF
 HVAC
 SYSTEMS IN A FIRE ALARM SYSTEM WITHOUT A CONSTANTLY
 ATTENDED
 LOCATION OR SUPERVISING STATION SHALL BE PERMITTED TO
 INITIATE AN
 ALARM SIGNAL.
 21.7.4.2 SMOKE DETECTORS MOUNTED IN THE AIR DUCTS OF
 HVAC
 SYSTEMS SHALL BE PERMITTED TO INITIATE AN ALARM SIGNAL
 WHERE
 REQUIRED BY OTHER GOVERNING LAWS, CODES, OR STANDARDS.
  
  
 PLEASE PROGRAM THE DUCT DETECTORS TO CAUSE A
 SUPERVISSORY SIGNAL PER THE APPLICABLE CODES.
  
  
 PETER LEDUC
 FIRE MARSHAL