Plan Review Notes
Plan Review Notes For Permit 18081474
Permit Number 18081474
Review Stop E
Sequence Number 1
Notes
Date Text
2018-09-17 07:22:40ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SHOW SIZE OF EXISITNG METER MAIN COMBO AND CONDUCTOR
 SIZES. SHOW SUB-PANELS BEING FROM FROM ATS'S AND
 CONDUCTOR SIZES. FBC 107.2.1
  
 2. PLANS SHOWS 6, #2/0 CONDUCTORS IN ONE 2'' CONDUIT.
 INSUFFICIENT SIZED CONDUIT. PROVIDE CORRECTION.
  
 END OF COMMENTS.
  