Plan Review Notes For Permit 18081472 |
Permit Number |
18081472 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-10-15 13:43:12 | REVIEW COMMENTS | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE SOUND TRANSMISSION TEST REPORTS THAT WE HAVE FOR | | THE PROFLEX 90 MSC THAT YOU ARE PROPOSING TO USE, | | REQUIRES AN 8? CONCRETE FLOOR SLAB WITH A SUSPENDED | | CEILING AND 3-1/2? OF FIBERGLASS INSULATION. THIS IS | | NOT THE CONDITION THAT EXITS FOR THIS PROJECT. I WOULD | | SUGGEST THAT YOU USE PROFLEX RCU 250 IF THAT SLAB IS 8 | | INCHES AND PROFLEX RCU 500 OR PROFLEX SUPER SIM 90 FOR | | A SIX INCH SLAB. FBC 1207.2, 1207.3 AND 603 | | |
|