2018-10-01 17:27:23 | NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW |
| COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- REVISE THE BALANCED RETURN AIR TRANSFER DUCT SIZE |
| SPECIFIED FOR SECONDARY BEDROOMS 2 AND 3. NEED AT LEAST |
| 9" DUCT FOR BEDROOM WITH 7" SUPPLY DUCT AND AT LEAST |
| 10" DUCT FOR BEDROOM WITH 8" SUPPLY DUCT AS REQUIRED BY |
| SEC. M1602.3 FBC-RESIDENTIAL. |
| |
| 2- PROVIDE THE NAME AND SIGNATURE OF THE PERSON |
| RESPONSIBLE FOR THE A/C DESIGN AS REQUIRED BY SEC. |
| 107.2.1 CITY AMENDMENTS. |
| |
| 3- REVISE THE HVAC LOAD CALCULATIONS: |
| A) THE FRONT DOOR OF THIS HOUSE DOESN'T FACE SOUTHEAST. |
| ACCORDING TO SEC. R403.7.1 FBC-ENERGY CONSERVATION |
| CALCULATIONS NEED TO BE DONE BASED ON THE ACTUAL |
| ORIENTATION OF THE BUILDING. |
| |
| B) CALCULATIONS ARE PREPARED BY GOARCH ENGINEERING, |
| INC. THE ENGINEER NEEDS TO SIGN AND SEAL CALCULATIONS |
| AS REQUIRED BY SEC. 61G15-23.001 FAC AND CHAPTER 471 |
| F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS. |
| |
| |
| |
| ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| |
| ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS. |
| |