2018-10-01 17:27:23NEW SINGLE FAMILY RESIDENCE (R3) MECHANICAL REVIEW
 COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- REVISE THE BALANCED RETURN AIR TRANSFER DUCT SIZE
 SPECIFIED FOR SECONDARY BEDROOMS 2 AND 3. NEED AT LEAST
 9" DUCT FOR BEDROOM WITH 7" SUPPLY DUCT AND AT LEAST
 10" DUCT FOR BEDROOM WITH 8" SUPPLY DUCT AS REQUIRED BY
 SEC. M1602.3 FBC-RESIDENTIAL.
  
 2- PROVIDE THE NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE A/C DESIGN AS REQUIRED BY SEC.
 107.2.1 CITY AMENDMENTS.
  
 3- REVISE THE HVAC LOAD CALCULATIONS:
 A) THE FRONT DOOR OF THIS HOUSE DOESN'T FACE SOUTHEAST.
 ACCORDING TO SEC. R403.7.1 FBC-ENERGY CONSERVATION
 CALCULATIONS NEED TO BE DONE BASED ON THE ACTUAL
 ORIENTATION OF THE BUILDING.
  
 B) CALCULATIONS ARE PREPARED BY GOARCH ENGINEERING,
 INC. THE ENGINEER NEEDS TO SIGN AND SEAL CALCULATIONS
 AS REQUIRED BY SEC. 61G15-23.001 FAC AND CHAPTER 471
 F.S. WHEN SUBMITTING DOCUMENTS FOR PUBLIC RECORDS.
  
  
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  