Plan Review Notes
Plan Review Notes For Permit 18081450
Permit Number 18081450
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-09-05 09:07:59FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED BY EMAIL ([email protected]) OR IN WRITING
 (FAX: 561-804-4774) AND APPROVED BY THE OFFICE OF THE
 FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 WHERE MUSIC SYSTEMS ARE BEING INSTALLED IN TENANT
 SPACES: THE SPEAKER SYSTEM WILL NEED TO BE TESTED
 AGAINST THE FIRE ALARM SYSTEM TO ENSURE THAT THE
 MINIMUM REQUIRED DECIBEL LEVELS OF THE FIRE ALARM
 SYSTEM ARE BEING MET. PENDING RESULTS OF FIELD
 INSPECTION/FIRE ALARM TEST, ADDITIONAL REQUIREMENTS MAY
 BE NEEDED.
  
 ALL TENANT SPACES FOR THE MARKETPLACE MUST BE TIED INTO
 THE MASTER FIRE ALARM PANEL FOR THE BUILDING. EACH
 TENANT SPACE WILL BE INTERCONNECTED AND UPON ACTIVATION
 OF AN ALARM IN ANY ONE SPACE, ALL SPACES WILL HAVE
 THEIR NOTIFICATION DEVICES ACTIVATE. AN FACP IN A
 TENANT SPACES WILL HAVE THE "RESET" AND "SILENCE"
 FUNCTIONS DEACTIVATED. RESET AND SILENCE OF AN ALARM IS
 LIMITED TO THE MASTER PANEL FOR THE BUILDING AND MAY
 ONLY BE DONE BY A LICENSED FIRE ALARM TECHNICIAN.
 SHOULD IT BE FOUND THAT TENANTS ARE ACCESSING THE
 PANELS IN THE TENANT SPACES AND/OR USING THE "RESET" OR
 "SILENCE" FUNCTIONS, THE OFFICE OF THE FIRE MARSHAL MAY
 REQUIRE THAT THE TENANT FACP BE REMOVED.
 PER APPROVED MASTER PLANS: MAIN FACP FOR THIS BUILDING
 IS TO BE THE ONLY PANEL TO NOTIFY THE FIRE DEPARMENT.
 NOTIFICATION WILL DESIGNATE SPECIFIC ADDRESS OF TENANT
 WHERE TROUBLE IS LOCATED.
  
 EACH BUILDING SHALL ALARM/EVACUATE ONLY THE SPACES IN
 THAT BUILDING (IE AN ALARM IN "B" WILL NOT EVACUATE ANY
 SPACE IN "A", "BII", OR "C". EACH TENANT SPACE FACP
 SHALL BE CONNECTED TO MAIN FACP FOR THIS BUILDING VIA
 MODULES. TENANT SYSTEM SHALL BE COMPATIBLE WITH
 NOTIFIER OR EQUAL APPROVED MAIN FACP/HARDWARE EACH
 FLOW/TAMPER SHALL BE ZONED SO THAT AN ALARM WILL SOUND
 FOR EACH BUILDING SEPARATELY.
  
 S. THOMAS
 561-804-4728
  