Plan Review Notes
Plan Review Notes For Permit 18081425
Permit Number 18081425
Review Stop P
Sequence Number 1
Notes
Date Text
2018-09-27 09:36:31ODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 1ST REVIEW:
 PERMIT 18081425
 PLUMBING COMMENTS: DENIED
  
 1. PROVIDE NOTE: PER FBC PL 416.5 TEMPERED WATER SHALL
 BE DELIVERED FROM LAVATORIES AND GROUP WASH FIXTURES
 LOCATED IN PUBLIC TOILET FACILITIES PROVIDED FOR
 CUSTOMERS, PATRONS AND VISITORS. TEMPERED WATER SHALL
 BE DELIVERED THROUGH AN APPROVED WATER-TEMPERATURE
 LIMITING DEVICE THAT CONFORMS TO ASSE 1070 OR CSA
 B125.3.
 2. URINAL TO COMPLY FBC ACC 605.2 PER FBC ACC 202.4.1
 3. FLUSH CONTROL FOR WC IN ADA COMPLIANT STALL TO BE
 LOCATED ON OPEN SIDE OF FIXTURE OR SHALL BE AUTOMATIC
 OPERATION COMPLYING WITH FBC ACC 605.6 PER FBC ACC
 202.4.1
 4. PROVIDE DIMENSIONS FOR ADA COMPLIANT GRAB BARS AT
 WATER CLOSET & DIMENSIONS FOR ADA COMPLIANT TOILET
 PAPER DISPENSERS PER FBC ACC 604.5, 604.7.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715