2018-10-04 15:55:42 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. VALUE APPEARS LOW FOR PROPOSED SCOPE OF WORK. |
| THE PERMIT VALUATION AND PERMIT FEE MUST BE |
| COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED |
| CONTRACTOR WOULD PROVIDE. |
| YOU MAY PROVIDE A COPY OF THE CONTRACT SIGNED BY THE |
| OWNER OR A LIST OF LABOR, MATERIALS AND EQUIPMENT |
| RENTAL TO VERIFY VALUE. |
| |
| CITY OF WPB CHPT. 1 ? VALUE |
| 109.3 BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF |
| THE BUILDING OFFICIAL, THE CLAIMED VALUATION OF |
| BUILDING, ALTERATION, STRUCTURE, ELECTRICAL, GAS, |
| MECHANICAL OR PLUMBING SYSTEMS APPEARS TO BE |
| UNDERESTIMATED ON THE APPLICATION, THE PERMIT SHALL BE |
| DENIED, UNLESS THE APPLICANT CAN SHOW DETAILED, |
| QUANTITY ESTIMATES, AND/OR BONA FIDE SIGNED CONTRACTS |
| (EXCLUDING LAND VALUE) TO MEET THE APPROVAL OF THE |
| BUILDING OFFICIAL. FOR PERMITTING PURPOSES, VALUATION |
| OF BUILDINGS AND SYSTEMS SHALL BE TOTAL REPLACEMENT |
| VALUE TO INCLUDE STRUCTURAL, ELECTRIC, PLUMBING, |
| MECHANICAL, INTERIOR FINISH, RELATIVE SITE WORK, |
| ARCHITECTURAL AND DESIGN FEES, MARKETING COSTS, |
| OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. |
| VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED |
| DATA OF NATIONAL CONSTRUCTION |
| COST ANALYSIS SERVICES (MARSHALL-SWIFT, MEANS, ETC.), |
| AS PUBLISHED BY INTERNATIONAL CODE CONGRESS. |
| FINAL BUILDING PERMIT VALUATION SHALL BE SET BY THE |
| BUILDING OFFICIAL. |
| |
| 2. PROVIDE ASTM TEST REPORTS FOR UNDERLAYMENT TO BE |
| USED UNDER HARD FLOORING. |
| THE FOLLOWING INFORMATION IS REQUIRED FOR ALL FLOORING |
| SUBMITTALS: |
| |
| 1. FLOOR PLAN WITH DIMENSIONS AND LOCATION OF WORK. |
| PROVIDED ON PLAN |
| *DESIGNER TO PRINT NAME AND SIGN PLAN PER FBC 107 * |
| PROVIDED ON PLAN |
| 2. TOTAL SQUARE FOOTAGE OF NEW FLOORING. PORCELAIN TILE |
| AREAS - PROVIDED ON PLAN |
| 3. TYPE OF PROPOSED FLOORING |
| (TILE/MARBLE/LAMINATE/WOOD/OTHER). PLANS SPECIFY |
| PORCELAIN TILE 12 X 24 |
| 4. STATED VALUE OF WORK. N/A THIS WILL BE INCLUDED IN |
| THE TOTAL VALUE ON APPLICATION. |
| 5. EXISTING SITE CONDITIONS: REQUIRED |
| A) THICKNESS OF SLAB. B) CEILING ASSEMBLY (OPEN |
| CONCRETE/SUSPENDED GYPSUM/ACOUSTICAL) |
| 6. PROPOSED UNDERLAYMENT. MUST BE FOR PROPOSED |
| FLOORING. |
| 7. TEST REPORTS FOR PROPOSED UNDERLAYMENT BASED ON |
| EXISTING SITE CONDITIONS. |
| 8. TEST REPORTS MAY BE BASED ON THE FOLLOWING ASTM?S, |
| E-84, E-90 & E-492. |
| 9. ALL DOCUMENTS SHALL BE SUBMITTED IN DUPLICATE. |
| |
| FBC 603.1 FLAME SPREAD ? ASTM E-84-09. N/A FOR TILE |
| |
| FBC 1207.2 AIR-BORNE SOUND. ASTM E ? 90-04 REQUIRED |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| FBC 1207.3 STRUCTURE-BORNE SOUND. ASTM E ? 492-09 |
| REQUIRED |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC SPACE OR SERVICE |
| AREA WITHIN THE STRUCTURE SHALL HAVE AN IMPACT |
| INSULATION CLASS (IIC) RATING OF NOT LESS THAN 50 (45 |
| IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E |
| 492. |
| |
| NOTE: CONDOMINIUM ASSOCIATION MAY REQUIRE HIGHER DB |
| VALUES. CHECK WITH PROPERTY MANAGER. |
| |
| |
| |
| |