2018-10-04 09:45:15 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| PLANS EXAMINER, PX3169 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. LIFE SAFETY PLAN LS-1W SUBMITTED FOR REVIEW DOES NOT |
| INDICATE LOCATION OF PROPOSED CONNECTION BRIDGE. |
| 2. PROVIDE FLOOR PLAN WITH ELEVATIONS IDENTIFYING |
| LOCATION OF PROPOSED CONNECTION BRIDGE. |
| 3. UPDATED UL ASSEMBLY SPECIFIES FIRE CAULKING BY 3M |
| COMPANY, TYPES FB 1000 NS, FB 1003 SL, FB 2000 AND FB |
| 2000 PLUS. ORIGINAL PERMITTED DOCUMENTS SPECIFIES FIRE |
| CAULKING TO BE ONE SOURCED, SPECIFICALLY HILTI PRODUCTS |
| FS ONE. PLEASE CLARIFY. |
| 4. DETAIL FOR CONNECTING BRIDGE SUBMITTED FOR REVIEW |
| INDICATES BRIDGE WILL BE SITE BUILT. |
| WELDED OR BOLTED CONNECTIONS |
| THE CONTRACTOR IS REQUIRED TO PROVIDE WELD PROCEDURE |
| SPECIFICATIONS & WELDER OPERATOR PERFORMANCE |
| QUALIFICATION RECORDS IN ACCORDANCE WITH THE REFERENCED |
| STANDARDS AT TIME OF INSPECTION. |
| 2017 FBC-B 2204.1 WELDING |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED AND MARK VOID. |
| |
| |