2018-09-12 17:11:55 | 09/12/2018 1ST PLUMBING REVIEW **DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. THERE IS A CLEAN OUT MISSING ON THE UNIT TO THE LEFT |
| OUTSIDE ENTERING THE BUILDING. 2017 FBC R3005.2.3 |
| BUILDING DRAIN AND BUILDING SEWER JUNCTION. |
| |
| 2. THE TOILET SHOWN ON THE ISOMETRIC IS A COMBO ON ITS |
| BACK AND IT MUST COMPLY WITH 2017 FBC PR 3005.1.3 HEEL- |
| OR SIDE-INLET QUARTER BENDS, VENTING. THE INLET IS |
| PERMITTED TO BE PLACED IN A HORIZONTAL POSITION ONLY |
| WHERE THE ENTIRE FITTING IS PART OF A DRY VENT |
| ARRANGEMENT. ALTERNATELY, A 4-INCH BY 3-INCH ELBOW |
| SHALL BE ACCEPTABLE WITH A 4-INCH, 2017 FBC R3005.1.4 |
| WATER CLOSET CONNECTION BETWEEN FLANGE AND PIPE. |
| 3. THERE IS A KITCHEN SINK BEHIND A BATHROOM AND IT IS |
| NOT ON THE ISOMETRIC DRAWING. IT HAS TO BE PICKED UP |
| DOWNSTREAM OF THE WATER CLOSET CANNOT DUMP INTO A WET |
| VENT BATHROOM GROUP. 2017 FBC R3108.1 HORIZONTAL WET |
| VENT PERMITTED. |
| 4. THERE IS A DRYER IN THAT BACK OF THE UNIT AT UTILITY |
| ROOM AND NO WASHING MACHINE, PLEASE TELL US IF THERE IS |
| A FACILITY CLOSE THAT HAS A WASHING MACHINE AVAILABLE |
| OR IS ONE BEING PROVIDED. IS SO PLEASE SHOW ON RISER |
| DIAGRAM. WPB AMENDMENTS TO THE FBC SEC. 107.2.1 |
| INFORMATION ON CONSTRUCTION DOCUMENTS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |