2018-09-01 18:53:23****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. SEE FIRE COMMENTS ON PERMIT APPLICATION 18070442
 REGARDING FIRE SPRINKLERS.
  
 THERE IS A LETTER REGARDING THE INTENT TO PROVIDE FIRE
 SPRINKLERS AND PERMIT DOCUMENTS, BUT THE DOCUMENTS WERE
 NOT PROVIDED; IN PARTICULAR, HYDRAULIC CALCS. IT IS NOT
 CLEAR IF EXISTING SERVICE IS SUFFICIENT TO PROVIDE
 SPRINKLERS TO THE PROPOSED STRUCTURE.
  
 IF FIRE DOES NOT REQUIRE THIS INFORMATION FOR THE
 FOUNDATION PERMIT, PLEASE ADVISE AND THIS COMMENT WILL
 BE REMOVED.
  
 2. OK
  
 3. FBC B CHAPTER 5, 6, 7, REVISE PLAN TO INCLUDE
 BUILDING TYPE, SQUARE FOOT AREA (GARAGE AND OFFICE
 SEPARATELY), SEPARATED OR NON SEPARATED OCCUPANCIES,
 NOTE THAT IT WILL BE A FIRE SPRINKLERED BUILDING,
 BUILDING HEIGHT, NUMBER OF STORIES.
  
 4. INFORMATION GENERALLY REQUIRED FOR A FOUNDATION
 PERMIT:
  
 PERMIT APPLICATION WHICH STATES SCOPE (FOR FOUNDATION
 PERMIT, TYPICALLY FOOTINGS OR FOOTINGS AND SLAB) -
 APPLICATION IN PROJECTDOX IS BLANK
 GEOTECHNICAL REPORT - NOT SUBMITTED
 SURVEY DRAWING - OK
 STORM WATER POLLUTION PREVENTION PLAN - NOT SUBMITTED
 SITE PLAN - OK
 1ST FLOOR ARCHITECTURAL PLAN - SUBMITTED BUT LACKS
 PROPOSED DFE (ELEVATION IN NAVD88)
 ARCHITECTURAL CROSS SECTION(S) OF THE BUILDING - NOT
 PROVIDED
 FOUNDATION PLAN - OK
 FOUNDATION DETAILS AND CROSS SECTIONS - OK
 STRUCTURAL ENGINEER'S GENERAL NOTES - OK
 UNDERGROUND PLUMBING PLAN - SUBMITTED, PENDING REVIEW
 ELECTRICAL PLAN SHOWING ANY UNDERGROUND CONDUIT -
 SUBMITTED, PENDING REVIEW
 ELECTRICAL GROUNDING TO STEEL DETAIL, IF APPLICABLE (OR
 EXPLAIN WHY THIS IS NOT APPLICABLE FOR THIS PROJECT).
 IF REQUIRED, A DETAIL IS REQUIRED AS A REVIEW, PERMIT,
 AND INSPECTION ARE REQUIRED PRIOR TO CONCRETE POUR -
 SUBMITTED, PENDING REVIEW
 PLAN SHOWING UNDERGROUND FIRE LINE - SUBMITTED, PENDING
 FIRE REVIEW (BLDG OK)
 THRESHOLD INSPECTION PLAN - NA
 SI OR RESIDENT INSPECTOR AGREEMENT (AS APPLICABLE) -
 RESIDENT INSPECTOR AGREEMENT REQUIRED (4000 PSI
 CONCRETE STRUCTURAL SLAB)
 THRESHOLD STATEMENT ON PLAN (IF APPLICABLE) - N/A, NOT
 THRESHOLD (RESIDENT)
  
 5. SHEET S1, I WAS UNABLE TO LOCATE A SPECIFICATION FOR
 F5, EITHER REVISE PLAN TO INCLUDE OR DIRECT AS TO WHERE
 THIS CAN BE LOCATED.
  
 6. FBC B 107.2.5, IT APPEARS THAT THIS IS LOCATED IN
 SFHA 7' NAVD88. S1 REFERS TO ARCHITECTURAL PAGES FOR
 ELEVATION; REVISE A1.1.1 TO INCLUDE (9' NAVD88 MINIMUM
 IS REQUIRED).
  
 7. FBC B 107.3.5.1.1(1), PROVIDE A "CONSTRUCTION
 DOCUMENTS" ELEVATION CERTIFICATE.
  
 8. THIS PERMIT WILL BE ISSUED WITH PROVISO:
  
 A. PRIOR TO CONCRETE POUR, A "BUILDING UNDER
 CONSTRUCTION" ELEVATION CERTIFICATE WILL BE REQUIRED.
 THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW.
 PRIOR TO FINAL INSPECTION BUT AFTER ALL MECHANICAL
 EQUIPMENT HAS BEEN INSTALLED AND FINAL GRADES
 COMPLETED, A "FINISHED CONSTRUCTION" ELEVATION
 CERTIFICATE WILL BE REQUIRED. THIS MAY BE SENT VIA
 EMAIL FOR PRELIMINARY REVIEW.
  
 B. THIS PERMIT IS ISSUED AT APPLICANT'S RISK PER FBC
 105.13:
  
 PHASED PERMIT APPROVAL. AFTER SUBMITTAL OF THE
 APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCT ION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION
 OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDER'S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE. ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE
 REQUIRED FOR THE FOLLOWING ITEMS AS APPLICABLE:
 LIGHT POLES/SITE LIGHTING
 FIRE ALARM
 FIRE SPRINKLER
 LOW VOLTAGE
 ACCESS
 LANDSCAPING
 IRRIGATION
 ALL OTHER ITEMS OTHER THAN BMEP
  