2018-09-01 18:53:23 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. SEE FIRE COMMENTS ON PERMIT APPLICATION 18070442 |
| REGARDING FIRE SPRINKLERS. |
| |
| THERE IS A LETTER REGARDING THE INTENT TO PROVIDE FIRE |
| SPRINKLERS AND PERMIT DOCUMENTS, BUT THE DOCUMENTS WERE |
| NOT PROVIDED; IN PARTICULAR, HYDRAULIC CALCS. IT IS NOT |
| CLEAR IF EXISTING SERVICE IS SUFFICIENT TO PROVIDE |
| SPRINKLERS TO THE PROPOSED STRUCTURE. |
| |
| IF FIRE DOES NOT REQUIRE THIS INFORMATION FOR THE |
| FOUNDATION PERMIT, PLEASE ADVISE AND THIS COMMENT WILL |
| BE REMOVED. |
| |
| 2. OK |
| |
| 3. FBC B CHAPTER 5, 6, 7, REVISE PLAN TO INCLUDE |
| BUILDING TYPE, SQUARE FOOT AREA (GARAGE AND OFFICE |
| SEPARATELY), SEPARATED OR NON SEPARATED OCCUPANCIES, |
| NOTE THAT IT WILL BE A FIRE SPRINKLERED BUILDING, |
| BUILDING HEIGHT, NUMBER OF STORIES. |
| |
| 4. INFORMATION GENERALLY REQUIRED FOR A FOUNDATION |
| PERMIT: |
| |
| PERMIT APPLICATION WHICH STATES SCOPE (FOR FOUNDATION |
| PERMIT, TYPICALLY FOOTINGS OR FOOTINGS AND SLAB) - |
| APPLICATION IN PROJECTDOX IS BLANK |
| GEOTECHNICAL REPORT - NOT SUBMITTED |
| SURVEY DRAWING - OK |
| STORM WATER POLLUTION PREVENTION PLAN - NOT SUBMITTED |
| SITE PLAN - OK |
| 1ST FLOOR ARCHITECTURAL PLAN - SUBMITTED BUT LACKS |
| PROPOSED DFE (ELEVATION IN NAVD88) |
| ARCHITECTURAL CROSS SECTION(S) OF THE BUILDING - NOT |
| PROVIDED |
| FOUNDATION PLAN - OK |
| FOUNDATION DETAILS AND CROSS SECTIONS - OK |
| STRUCTURAL ENGINEER'S GENERAL NOTES - OK |
| UNDERGROUND PLUMBING PLAN - SUBMITTED, PENDING REVIEW |
| ELECTRICAL PLAN SHOWING ANY UNDERGROUND CONDUIT - |
| SUBMITTED, PENDING REVIEW |
| ELECTRICAL GROUNDING TO STEEL DETAIL, IF APPLICABLE (OR |
| EXPLAIN WHY THIS IS NOT APPLICABLE FOR THIS PROJECT). |
| IF REQUIRED, A DETAIL IS REQUIRED AS A REVIEW, PERMIT, |
| AND INSPECTION ARE REQUIRED PRIOR TO CONCRETE POUR - |
| SUBMITTED, PENDING REVIEW |
| PLAN SHOWING UNDERGROUND FIRE LINE - SUBMITTED, PENDING |
| FIRE REVIEW (BLDG OK) |
| THRESHOLD INSPECTION PLAN - NA |
| SI OR RESIDENT INSPECTOR AGREEMENT (AS APPLICABLE) - |
| RESIDENT INSPECTOR AGREEMENT REQUIRED (4000 PSI |
| CONCRETE STRUCTURAL SLAB) |
| THRESHOLD STATEMENT ON PLAN (IF APPLICABLE) - N/A, NOT |
| THRESHOLD (RESIDENT) |
| |
| 5. SHEET S1, I WAS UNABLE TO LOCATE A SPECIFICATION FOR |
| F5, EITHER REVISE PLAN TO INCLUDE OR DIRECT AS TO WHERE |
| THIS CAN BE LOCATED. |
| |
| 6. FBC B 107.2.5, IT APPEARS THAT THIS IS LOCATED IN |
| SFHA 7' NAVD88. S1 REFERS TO ARCHITECTURAL PAGES FOR |
| ELEVATION; REVISE A1.1.1 TO INCLUDE (9' NAVD88 MINIMUM |
| IS REQUIRED). |
| |
| 7. FBC B 107.3.5.1.1(1), PROVIDE A "CONSTRUCTION |
| DOCUMENTS" ELEVATION CERTIFICATE. |
| |
| 8. THIS PERMIT WILL BE ISSUED WITH PROVISO: |
| |
| A. PRIOR TO CONCRETE POUR, A "BUILDING UNDER |
| CONSTRUCTION" ELEVATION CERTIFICATE WILL BE REQUIRED. |
| THIS MAY BE SENT VIA EMAIL FOR PRELIMINARY REVIEW. |
| PRIOR TO FINAL INSPECTION BUT AFTER ALL MECHANICAL |
| EQUIPMENT HAS BEEN INSTALLED AND FINAL GRADES |
| COMPLETED, A "FINISHED CONSTRUCTION" ELEVATION |
| CERTIFICATE WILL BE REQUIRED. THIS MAY BE SENT VIA |
| EMAIL FOR PRELIMINARY REVIEW. |
| |
| B. THIS PERMIT IS ISSUED AT APPLICANT'S RISK PER FBC |
| 105.13: |
| |
| PHASED PERMIT APPROVAL. AFTER SUBMITTAL OF THE |
| APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING |
| OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE |
| CONSTRUCT ION OF FOUNDATIONS OR ANY OTHER PART OF A |
| BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS |
| FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN |
| SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION |
| OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED |
| AT THE HOLDER'S OWN RISK WITH THE BUILDING OPERATION |
| AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE |
| STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED |
| TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS |
| PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE. ALL |
| OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST |
| BE SECURED PRIOR TO THIS PROVISION BEING APPLIED. |
| |
| C. SEPARATE PERMITS (APPLICATIONS, PLANS, AND FEES) ARE |
| REQUIRED FOR THE FOLLOWING ITEMS AS APPLICABLE: |
| LIGHT POLES/SITE LIGHTING |
| FIRE ALARM |
| FIRE SPRINKLER |
| LOW VOLTAGE |
| ACCESS |
| LANDSCAPING |
| IRRIGATION |
| ALL OTHER ITEMS OTHER THAN BMEP |
| |