2018-11-26 16:02:31 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18081364 |
| REVIEWED: SEPTEMBER 10, 2018 |
| 2ND REVIEW NOVEMBER 26, 2018 |
| |
| THE PREVIOUS COMMENTS WERE REQUESTING TEST REPORTS FOR |
| THE UNDERLAYMENT. |
| WHAT WAS SUBMITTED IS A DATA SHEET, BUT IT DOESN'T |
| PROVIDE THE TEST REPORT FOR THE CONDITION OF |
| INSTALLATION. |
| THE TEST REPORT CONSIDER THE MATERIAL BEING INSTALLED |
| OVER THE UNDERLAYMENT AND THE THICKNESS OF MATERIAL |
| BELOW (USUALLY SLAB THICKNESS) |
| PLEASE CONTACT ME TO DISCUSS WHICH PRODUCTS WE HAVE |
| ALREADY APPROVED, OR WHAT IS NEEDED FOR THE SAM 3 SOUND |
| CONTROL THAT WAS SUBMITTED. |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE |
| PROPOSED? PLEASE ADVISE VIA EMAIL. IF THE UNDERLAYMENT |
| PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST |
| REPORTS ON FILE, THE FOLLOWING REPORTS ARE REQUIRED: |
| |
| MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| |
| A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| |
| C. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723. |
| |
| PLEASE FEEL TO CONTACT ME VIA PHONE OR E-MAIL WITH ANY |
| QUESTIONS. |
| |