2018-12-21 09:16:47 | PROVISO: |
| FLOORING SUBMITTAL TO BE PROVIDED PRIOR TO FLLORING |
| INSTALLATION. |
| |
| PLEASE ADVISE, WHAT FLOORING AND UNDERLAYMENT ARE |
| PROPOSED? PLEASE ADVISE VIA EMAIL. IF THE UNDERLAYMENT |
| PRODUCT PROPOSED IS NOT ONE FOR WHICH WE HAVE TEST |
| REPORTS ON FILE, THE FOLLOWING REPORTS ARE REQUIRED: |
| [FBC 1207.2]AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS AND SLEEPING UNITS FROM EACH |
| OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A |
| SOUND TRANSMISSION CLASS OF NOT LESS THAN 50, OR NOT |
| LESS THAN 45 IF FIELD TESTED, FOR AIR-BORNE NOISE WHEN |
| TESTED IN ACCORDANCE WITH ASTM E90. |
| [FBC 1207.3]STRUCTURE-BORNE SOUND. FLOOR/CEILING |
| ASSEMBLIES |
| BETWEEN DWELLING UNITS AND SLEEPING UNITS OR BETWEEN A |
| DWELLING |
| UNIT OR SLEEPING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN |
| THE STRUCTURE SHALL HAVE AN IMPACT INSULATION CLASS |
| RATING OF |
| NOT LESS THAN 50, OR NOT LESS THAN 45 IF FIELD TESTED, |
| WHEN TESTED |
| IN ACCORDANCE WITH ASTM E492. |
| [FBC 603.1]ALLOWABLE MATERIALS IN NON COMBUSTIBLE |
| BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| OR UL 723. |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |