Plan Review Notes
Plan Review Notes For Permit 18081343
Permit Number 18081343
Review Stop B
Sequence Number 1
Notes
Date Text
2018-10-17 14:12:23****CORRECTIONS****
 W.P.B. PERMIT: 18081343 (8TH FLOOR)
 REVIEWED: OCTOBER 16, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
  
 1. [FBC AMENDED 107.2.1]ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS AND ACCOMPANYING DATA SHALL BEAR THE
 NAME AND SIGNATURE OF THE PERSON RESPONSIBLE FOR THE
 DESIGN.
 ALL SHEETS NEED GRAPHIC REPRESENTATION OF SEAL TO
 INCLUDE FLORIDA LICENSE NUMBER, NAME AND SIGNATURE OF
 ARCHITECT.
 ALSO, REMOVE THE NOTE FROM TITLE BLOCK THAT STATES
 ?PRELIMINARY DRAWINGS NOT TO USED FOR RECORDING,
 PERMITTING OR CONSTRUCTION?
  
 2. [FBC AMENDED 107.2.1]WHEN RELOADING DRAWINGS MAKE
 SURE EACH SHEET IS DIGITALLY SIGNED. THIS WILL TAKE
 CARE OF THE SIGNATURE REVIEW THAT HAS FAILED 2ND ROUND
 REVIEW.
  
 3. [FBC AMENDED 107.2.5]PROJECT DATA
 SPECIFY THE AFFECTED AREA ON EACH FLOOR AND THE
 OCCUPANCY OF THE AREAS. CONSTRUCTION TYPE, SPRINKLED OR
 NON, FINISH FIRE CLASSIFICATION.
 GENERAL FINISH NOTES STATE TO COMPLY WITH IBC 804 AND
 804.3. PLEASE REMOVE THIS NOTE AND CHANGE TO FLORIDA
 BUILDING CODE REFERENCES.
  
 4. [FBC AMENDED 107.2.5]ARE THERE ANY PENETRATIONS INTO
 EXISTING MAIN STRUCTURE DUE TO THIS WORK ON THE 8TH
 FLOOR? IF YES PLEASE PROVIDE DETAILS OF FIRE STOPPING.
  
 5. [FBC AMENDED 107.2.5]SHEET I-180 HAS CALL OUTS IN
 THE LOUGE THAT REFER TO SHEET I-452. PLEASE INSERT THIS
 SHEET, OR CHANGE CALL OUTS TO THE PAGE WHERE THE
 ELEVATIONS CAN BE FOUND.
  
 6. [FBC AMENDED 107.2.5]THE VALUE OF THIS WORK IS MORE
 THAN THE 5TH AND 6TH FLOOR BECAUSE IT INCLUDES THE
 RESIDENTIAL UNITS. IT IS UNCLEAR FROM THE DEMO PLANS
 WHAT IS BEING DONE IN THE UNITS. PLEASE PROVIDE
 DESCRIPTION OF WHAT IS BEING DONE TO THE RESIDENTIAL
 UNITS. IS IT JUST PAINT OR IS FLOORING INCLUDED. IF
 FLOORING IS BEING REPLACED PLEASE INCLUDE SUBMITTAL FOR
 IIC, STC AND FLAME SPREAD, OR INDICATE THAT IT WILL BE
 DEFERED.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  