Plan Review Notes
Plan Review Notes For Permit 18081296
Permit Number 18081296
Review Stop M
Sequence Number 1
Notes
Date Text
2018-09-20 08:45:481ST REVIEW FBC-2010 MECHANICAL
 REVISION #18081296
 9/20/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE- 2010
 FBC M- FLORIDA MECHANICAL CODE- 2010
 FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC- 2010
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M2-90: TWO OF THE THREE HP'S IN THE TENANT
 SPACE ARE NOT LABELED- SECTION 107.2.1 WPB.
  
 2) M2-90: DUCT SMOKE DETECTORS ARE REQUIRED IN THE
 SUPPLY SYSTEMS OF ALL 5-TON HP'S, AND IN THE HP CLOSETS
 SHARING THE COMMON RETURN AIR PLENUM- SECTIONS 606.2.1
 & 606.2.2 FBC M.
  
 3) VERIFY THE DRYER EXHAUST DUCT IS NOT RUNNING THROUGH
 THE RETURN AIR PLENUM- SECTION 504.4 FBC M
  
 4) VERIFY ALL MATERIALS IN THE HP CLOSETS WILL BE
 NON-COMBUSTIBLE, OR WILL HAVE A FLAME SPREAD/SMOKE
 DEVELOPED INDEX OF NOT MORE THAN 25-50- SEE SECTION
 602.2.1 FBC M.
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE COOKING
 APPLIANCES, KITCHEN HOOD AND EXHAUST DUCT, AND CLOTHES
 DRYER.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  