Plan Review Notes For Permit 18081289 |
Permit Number |
18081289 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-09-19 10:23:43 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) AN 8' GATE IS INDICATED ON THE PARKING LOT SIDE. FD | | ACCESS REQUIRES A 20' ACCESS OPENING. | | | | A 20' GATE IS NOT NEEDED ALONG THE ALLEY WAY. | | | | PLEASE REVIEW AND PROVIDE. | | | | | | | | 2) THERE ARE NO OPENINGS INDICATED ALONG EVERNIA ST. A | | 4' GATE AT THE STEPS ON EVERNIA IS NEEDED FOR BUILDING | | ACCESS FOR FD. | | | | PLEASE REVIEW AND PROVIDE. | | | | | | | | 3) A KNOX PADLOCK IS RECOMMENDED FOR FD ACCESS AND SITE | | SECURITY AT EACH GATE. | | | | | | | | | | 4) THE TITLE BLOCK DOES NOT INCLUDE A STREET ADDRESS. | | | | PLEASE PROVIDE THE STREET ADDRESS OF THE BUILDING ON | | THE TITLE BLOCK | | | | ADDITIONALLY, THE BUILDING ADDRESS SHALL REMAIN VISIBLE | | AND/OR ADDITIONAL SIGNAGE SHALL PLACED ALONG THE FENCE | | FOR IDENTIFICATION PURPOSES. | | | | | | | | 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | | | 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|