Plan Review Notes For Permit 18081283 |
Permit Number |
18081283 |
|
Review Stop |
FIRE |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-09-24 08:59:47 | THE PROPOSED PROJECT INDICATES THE USE OF FLEX DROP | | PIPING. THE EXISTING SYSTEM APPEARS TO A TYPICAL ARM | | OVER. | | FLEX DROPS TYPICALLY HAVE A HIGHER FRICTION LOSS THAN | | THE DESIGNED ARM OVER SYSTEM. | | THERE IS NO HYDRAULIC CALCULATION SHEET SUBMITTED THAT | | SHOWS THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE | | EXISTING SYSTEM DESIGN TO PROVIDE THE REQUIRED WATER | | FLOW. | | PLEASE PROVIDE CALCULATIONS DETAILS. | | | | |
|