Plan Review Notes For Permit 18081283 |
Permit Number |
18081283 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-09-14 14:05:53 | 1.)THE PROPOSED PROJECT INDICATES THE USE OF FLEX DROP | | PIPING. THE EXISTING SYSTEM APPEARS TO A TYPICAL ARM | | OVER. | | FLEX DROPS TYPICALLY HAVE A HIGHER FRICTION LOSS THAN | | THE DESIGNED ARM OVER SYSTEM. | | THERE IS NO HYDRAULIC CALCULATION SHEET SUBMITTED THAT | | SHOWS THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE | | EXISTING SYSTEM DESIGN TO PROVIDE THE REQUIRED WATER | | FLOW. | | PLEASE PROVIDE CALCULATIONS DETAILS OR USE THE SAME | | TYPE OF ARM OVER THAT MATCHES THE EXISTING SYSTEM | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. |
|