Plan Review Notes For Permit 18081283
Permit Number 18081283
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-09-14 14:05:531.)THE PROPOSED PROJECT INDICATES THE USE OF FLEX DROP
 PIPING. THE EXISTING SYSTEM APPEARS TO A TYPICAL ARM
 OVER.
 FLEX DROPS TYPICALLY HAVE A HIGHER FRICTION LOSS THAN
 THE DESIGNED ARM OVER SYSTEM.
 THERE IS NO HYDRAULIC CALCULATION SHEET SUBMITTED THAT
 SHOWS THAT THE NEW FLEX DROPS WILL BE SUPPORTED BY THE
 EXISTING SYSTEM DESIGN TO PROVIDE THE REQUIRED WATER
 FLOW.
 PLEASE PROVIDE CALCULATIONS DETAILS OR USE THE SAME
 TYPE OF ARM OVER THAT MATCHES THE EXISTING SYSTEM
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.