Plan Review Notes
Plan Review Notes For Permit 18081281
Permit Number 18081281
Review Stop B
Sequence Number 2
Notes
Date Text
2018-11-15 18:52:13PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION IS DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENGINEER'S SEAL IS A PHOTOCOPY. THE RAS 117
 CALCULATIONS ARE REQUIRED TO HAVE THE FLORIDA
 ENGINEER'S SEAL AND ORIGINAL HANDWRITTEN SIGNATURE,
 COPIES OR OTHER FACSIMILES ARE NOT ACCEPTABLE. FAC
 61G15 - 23.002 DIGITAL SIGNATURES ARE ONLY ACCEPTABLE
 FOR ELECTRONICALLY TRANSMITTED PLANS AND DOCUMENTS.
  
 2) PAGE 1 OF THE RAS 117 CALCULATIONS UNDER DECK SYSTEM
 TYPE, FASTENING OPTION #4 FROM THE NOA IS SPECIFIED.
 THIS SHOULD BE OPTION #5 SINCE THAT IS THE ONLY ONE
 THAT HAS A -60 PSF. FBC 107.2.1
  
  