Plan Review Notes For Permit 18081281 |
Permit Number |
18081281 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-30 07:11:55 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | REVISION IS DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED, NOA NO. | | 15-1020.01, HAS FASTENING OPTION #3 WITH A MAXIMUM | | DESIGN PRESSURE OF -52.2 PSF FOR A NON-INSULATED WOOD | | DECK SPECIFIED ON PAGE 51 OF 67. THE SIGNED AND SEALED | | RAS 117 CALCULATIONS THAT WERE SUBMITTED ARE SPECIFIC | | TO THIS ASSEMBLY. IN ORDER TO ADD INSULATION TO THIS | | PROJECT, YOU ARE REQUIRED TO SUBMIT THE PRODUCT | | APPROVALS FOR A ROOFING SYSTEM WITH AN INSULATED DECK | | AND SPECIFY THE FASTENING OPTION THAT WILL BE USED. TWO | | SETS OF SIGNED AND SEALED RAS117 CALCULATIONS FOR THE | | SELECTED ASSEMBLY WILL BE REQUIRED IF THE DESIGN | | PRESSURES ARE NOT ADEQUATE FOR ALL ROOF ZONES. | | | | 2) THE INCREASED VALUE OF WORK IS SPECIFIED AS $0.00 ON | | THE REVISION FORM. THE ACTUAL AMOUNT OF THE EXTRA COST | | TO ADD INSULATION TO THIS PROJECT SHOULD BE SPECIFIED | | ON THE FORM. | | | | | | | | | | | | | | | | | | | | |
|