Plan Review Notes
Plan Review Notes For Permit 18081281
Permit Number 18081281
Review Stop B
Sequence Number 1
Notes
Date Text
2018-08-30 07:11:55PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 REVISION IS DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED, NOA NO.
 15-1020.01, HAS FASTENING OPTION #3 WITH A MAXIMUM
 DESIGN PRESSURE OF -52.2 PSF FOR A NON-INSULATED WOOD
 DECK SPECIFIED ON PAGE 51 OF 67. THE SIGNED AND SEALED
 RAS 117 CALCULATIONS THAT WERE SUBMITTED ARE SPECIFIC
 TO THIS ASSEMBLY. IN ORDER TO ADD INSULATION TO THIS
 PROJECT, YOU ARE REQUIRED TO SUBMIT THE PRODUCT
 APPROVALS FOR A ROOFING SYSTEM WITH AN INSULATED DECK
 AND SPECIFY THE FASTENING OPTION THAT WILL BE USED. TWO
 SETS OF SIGNED AND SEALED RAS117 CALCULATIONS FOR THE
 SELECTED ASSEMBLY WILL BE REQUIRED IF THE DESIGN
 PRESSURES ARE NOT ADEQUATE FOR ALL ROOF ZONES.
  
 2) THE INCREASED VALUE OF WORK IS SPECIFIED AS $0.00 ON
 THE REVISION FORM. THE ACTUAL AMOUNT OF THE EXTRA COST
 TO ADD INSULATION TO THIS PROJECT SHOULD BE SPECIFIED
 ON THE FORM.
  
  
  
  
  
  
  
  
  
  