2018-09-17 09:57:22 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #18081266 |
| 9/17/18 |
| |
| CODES IN EFFECT: |
| |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) VERIFY COMPLIANCE WITH SECTION 506.3.6 FBC M: GREASE |
| EXHAUST DUCTS NOT IN ENCLOSURES SHALL HAVE A MINIMUM |
| 18" CLEARANCE TO COMBUSTIBLES. |
| |
| 2) VERIFY COMPLIANCE WITH SECTIONS 508.1 AND 401.4 AND |
| PROVIDE THE REQUIRED CLEARANCE DISTANCE MEASUREMENTS |
| FOR THE MAKEUP AIR OPENING TO PROPERTY LINES, ADJOINING |
| GRADE, STREETS, ALLEYS, OR PARKING LOTS ETC. |
| |
| 3) CLARIFY HOW THE MAKEUP AIR OPENING WILL BE |
| PROTECTED. WILL AN IMPACT AND WIND RESISTANT LOUVER BE |
| INSTALLED? SUBMIT A PRODUCT DATA SHEET FOR THE GRILL |
| AND HOOD, AND A MIAMI-DADE NOA OR FL. PRODUCT APPROVAL- |
| SECTION 401.5 FBC M |
| |
| 4) INDICATE THE EXHAUST DUCT TERMINATION HEIGHT ABOVE |
| THE ROOF AND PROVIDE A ROOF PLAN THAT SHOWS CLEARANCE |
| DISTANCES FROM EF-1 TO MECHANICAL OR GRAVITY O/A |
| OPENINGS INTO THE BUILDING, AND TO THE ROOF EDGES- |
| SECTIONS 506.3.13.1, 506.3.13.3 AND 304.11 FBC M |
| |
| 5) PROVIDE THE WIND LOAD DESIGN CRITERIA USED TO |
| DETERMINE THE ANHORING AND TIE DOWN METHODS FOR EF-1 |
| SYSTEM, THE ROOFTOP DUCTWORK, AND SUPPORTS- SECTION |
| 301.15 FBC M |
| |
| 6) VERIFY THE TEMPERATURE DIFFERENTIAL BETWEEN THE |
| MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL |
| NOT EXCEED 10 DEGREES FAHRENHEIT- SECTION 508.1.1 FBC M |
| |
| 7) ADVISORY: ISSUANCE OF THE HOOD PERMIT IS CONTINGENT |
| ON THE GENERAL CONTRACTOR OBTAINING A PERMIT FOR THE |
| NEW RESTARAUNT BUILD-OUT INCLUDING THE GAS-FIRED |
| COOKING APPLIANCES, AND SUB-PERMIT FOR THE GAS PIPING. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |