Plan Review Notes
Plan Review Notes For Permit 18081266
Permit Number 18081266
Review Stop M
Sequence Number 1
Notes
Date Text
2018-09-17 09:57:221ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18081266
 9/17/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) VERIFY COMPLIANCE WITH SECTION 506.3.6 FBC M: GREASE
 EXHAUST DUCTS NOT IN ENCLOSURES SHALL HAVE A MINIMUM
 18" CLEARANCE TO COMBUSTIBLES.
  
 2) VERIFY COMPLIANCE WITH SECTIONS 508.1 AND 401.4 AND
 PROVIDE THE REQUIRED CLEARANCE DISTANCE MEASUREMENTS
 FOR THE MAKEUP AIR OPENING TO PROPERTY LINES, ADJOINING
 GRADE, STREETS, ALLEYS, OR PARKING LOTS ETC.
  
 3) CLARIFY HOW THE MAKEUP AIR OPENING WILL BE
 PROTECTED. WILL AN IMPACT AND WIND RESISTANT LOUVER BE
 INSTALLED? SUBMIT A PRODUCT DATA SHEET FOR THE GRILL
 AND HOOD, AND A MIAMI-DADE NOA OR FL. PRODUCT APPROVAL-
 SECTION 401.5 FBC M
  
 4) INDICATE THE EXHAUST DUCT TERMINATION HEIGHT ABOVE
 THE ROOF AND PROVIDE A ROOF PLAN THAT SHOWS CLEARANCE
 DISTANCES FROM EF-1 TO MECHANICAL OR GRAVITY O/A
 OPENINGS INTO THE BUILDING, AND TO THE ROOF EDGES-
 SECTIONS 506.3.13.1, 506.3.13.3 AND 304.11 FBC M
  
 5) PROVIDE THE WIND LOAD DESIGN CRITERIA USED TO
 DETERMINE THE ANHORING AND TIE DOWN METHODS FOR EF-1
 SYSTEM, THE ROOFTOP DUCTWORK, AND SUPPORTS- SECTION
 301.15 FBC M
  
 6) VERIFY THE TEMPERATURE DIFFERENTIAL BETWEEN THE
 MAKEUP AIR AND THE AIR IN THE CONDITIONED SPACE SHALL
 NOT EXCEED 10 DEGREES FAHRENHEIT- SECTION 508.1.1 FBC M
  
 7) ADVISORY: ISSUANCE OF THE HOOD PERMIT IS CONTINGENT
 ON THE GENERAL CONTRACTOR OBTAINING A PERMIT FOR THE
 NEW RESTARAUNT BUILD-OUT INCLUDING THE GAS-FIRED
 COOKING APPLIANCES, AND SUB-PERMIT FOR THE GAS PIPING.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  